SG-150-1 33
Name
Possible
values
Default
Description
Modbus
type & addr
High, 4=SDT High, 5=SST High,
SDT High, 6=SST High, 7=SST
High, SDT Low, 8=SDT Low)
Discharge
temperature
unit °C
scale 10
sint16
-
Discharge temperature
IR 12010
AUX temperature
unit °C
scale 10
sint16
-
AUX temperature
IR 12011
High Pressure Switch
unit None
scale 1
uint8
-
High pressure switch
(0=Off, 1=On)
IR 12022
Crank Case Oil Heater
unit None
scale 1
uint8
-
Crank case oil heater
(0=Off, 1=On)
IR 12023
Oil injection valve
unit None
scale 1
uint8
-
Oil injection valve
(0=Off, 1=On)
IR 12024
Oil Sensor 1
unit None
scale 1
uint8
-
Oil Sensor 1
(0=Off, 1=On)
IR 12025
Oil Sensor 2
unit None
scale 1
uint8
-
Oil Sensor 2
(0=Off, 1=On)
IR 12026
Motor start is
requested
unit None
scale 1
uint8
-
Motor start is requested
(0=Off, 1=On)
IR 12027
Liquid injection
cooling valve
unit None
scale 1
uint8
-
Liquid injection cooling valve
(0=Off, 1=On)
IR 12029
Note 1: For future compressor versions

Table of Contents

Other manuals for Bitzer CM-SW-01

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bitzer CM-SW-01 and is the answer not in the manual?

Bitzer CM-SW-01 Specifications

General IconGeneral
BrandBitzer
ModelCM-SW-01
CategoryControl Unit
LanguageEnglish

Related product manuals