.4.2 CM-SW-01
Standard for all CSW105 compressors
The compressor module integrates the entire electronic
periphery of the compressor: It allows monitoring the
essential operating parameters of the compressor: mo-
tor and discharge gas temperature, phase and rotation
direction monitoring, oil supply and application limits
and thus protects the compressor from operation under
critical conditions. For further information, see Tech-
nical Information ST-150.
!
!
NOTICE
The compressor module may be damaged or
fail!
Never apply any voltage to the terminals of CN7
to CN12 not even for test purposes!
The voltage applied to the terminals of CN13
must not exceed 10V!
The voltage applied to terminal 3 of CN14 must
not exceed 24V! Do no apply voltage to the
other terminals!
The following components are completely installed and
wired in the state of delivery:
Slider position indicator.
Oil monitoring (OLC-D1).
Solenoid valves for capacity control and V
i
.
Discharge gas temperature sensor.
Low pressure and high pressure transmitter.
Modification to these components or their wiring is not
required and should not be done without consulting
BITZER.
The following components are not installed and wired in
the state of delivery and need to be connected:
Motor temperature monitoring (PTC sensor in motor
winding).
Phase monitoring (in case of a phase failure or inad-
missibly high phase asymmetry).
The compressor module internally supplies voltage to
the peripheral devices (solenoid valves, oil monitoring
device and slider position indicator) and to the terminal
strips CN7 to CN12.
Please refer to the Technical Information ST-150 for in-
formation on all connections.
5
.4.3 SE-i1
This protection device with extended monitoring func-
tions can be used as an option for all HS.53 .. HS.85
compressors and CSH and CSW compressors.
Monitoring functions:
Temperature monitoring.
Monitoring of the PTC control circuit to detect any
short-circuit or line break/sensor failure.
Rotation direction monitoring.
Monitoring of phase failure and asymmetry.
Monitoring of the maximum cycling rate.
For further information, see Technical Information
CT-110.
5
.4.4 SE-E2
Optional protection device for operation with frequency
inverter and soft starter (for a ramp time shorter than
1s).
Dimensions and integration in the control identical to
SE-E1.
Suitable for all CS. compressors.
Monitoring functions are basically identical to those
of SE-E1. However, the SE-E2 monitors phase fail-
ure during the entire running time of the compressor.
For further information, see Technical Information
ST-122.
5
.4.5 Monitoring of the oil circuit
For short circuits without liquid injection (LI) for addi-
tional cooling and for small system volume and small
refrigerant charge: Indirect monitoring with oil tem-
perature sensor (standard)
!
!
NOTICE
Lack of oil leads to a too high increase in tem-
perature.
Risk of damage to the compressor!
For circuits with liquid injection (LI) for additional
cooling and / or for great system volume as well as
parallel compounding: Monitor oil level directly with
opto-electronic oil level monitoring (option), see
chapter Opto-electronic oil level monitoring OLC-D1-
S, page 26. The connection is on the compressor
housing, see chapter Connections and dimensional
drawings, page 14, position 8.
SB-170-9
Semi-hermetic compact screw compressors
Translation of the original Operating Instructions
English....................................................................................................................................................... 2
Halbhermetische Kompaktschraubenverdichter
Originalbetriebsanleitung
Deutsch ..................................................................................................................................................... 35
Compresseurs à vis compacts hermétiques accessibles
Traduction des instructions de service d'origine
Français..................................................................................................................................................... 68
CSH6553-35Y..CSH6593-60Y
CSH7553-50Y .. CSH7593-110(Y)
CSH8553-80Y .. CSH8593-180(Y)
CSH9553-180(Y) .. CSH95113-320Y
CSH7673-70Y .. CSH7693-90Y
CSH8673-110Y .. CSH8693-140Y
CSH9663-160Y .. CSH96113-320Y
CSK6151-50 .. CSK6161-60
CSW6583-40Y .. CSW6593-60(Y)
CSW7571-60Y .. CSW7593-90(Y)
CSW8573-90Y .. CSW8593-140(Y)
CSW9563-140Y .. CSW95113-320(Y)
CSW10593-400Y
D
ocument for installers
Dokument für Monteure
Document pour des monteurs
ИНСТРУКЦИЯ ПО ЭКСПЛУАТАЦИИ
SB-170-9 RUS
Полугерметичные компактные винтовые компрессоры
Перевод оригинальной инструкции по эксплуатации
Русский …………………………………………………………………………………………………................. 68
Для монтажников

Table of Contents

Question and Answer IconNeed help?

Do you have a question about the Bitzer CSH6553-35Y and is the answer not in the manual?

Bitzer CSH6553-35Y Specifications

General IconGeneral
ModelCSH6553-35Y
Frequency50/60 Hz
Cooling CapacityData varies with refrigerant and operating conditions. See performance data.
RefrigerantR134a, R407C, R404A, R507
Suction Line Connection54 mm
Power InputData varies with refrigerant and operating conditions. See performance data.
TypeSemi-Hermetic Screw Compressor

Summary

2 Safety

2.1 Authorized staff

Specifies requirements for qualified and authorized personnel performing work on compressors and refrigeration systems.

2.2 Residual risks

Details unavoidable residual risks associated with the compressor and emphasizes reading the operating instructions.

2.3 Safety references

Instructions and guidelines to prevent hazards, emphasizing strict observance.

4 Mounting

3.2 Use of flammable refrigerants of the A2L safety group (e.g. R1234yf)

Covers safety regulations and residual risks when using flammable refrigerants of the A2L safety group.

4.1 Transporting the compressor

Provides instructions and safety precautions for transporting the compressor, including weight and lifting information.

4.2 Installing the compressor

Details requirements for horizontal installation, considering extreme conditions and system connections.

4.3 Connecting the pipelines

Covers safety precautions and procedures for connecting pipelines, including pipe connections and shut-off valves.

5 Electrical connection

5.1 Mains connections

Provides guidance on dimensioning motor contactors, feed lines, and fuses for mains connections.

5.2 Motor versions

Describes part-winding and star-delta motor versions, including starting modes and connection instructions.

5.4 Protection devices

Covers safety warnings related to electrical shock and potential failures due to improper connections.

5.4.2 CM-SW-01

Details the CM-SW-01 compressor module, its integrated functions, and components.

6 Commissioning

6.1 Checking pressure strength

Details procedures for checking refrigerant circuit pressure strength, including test pressures and safety.

6.2 Checking tightness

Explains how to check the refrigerant circuit for tightness using excess pressure, preferably with dried nitrogen.

6.4 Charging refrigerant

Outlines procedures for charging refrigerant, including safety warnings and quantity measurement.

6.6 Compressor start

Details the process of starting the compressor, including crucial checks and procedures.

6.6.1 Checking the rotation direction

Explains how to test and verify the correct rotation direction of the compressor motor.

7 Operation

8 Maintenance

8.1 Oil change

Covers procedures for oil change, including warnings about ester oil degradation and handling precautions.

9 Decommissioning