EasyManua.ls Logo

Bitzer ECOLITE Series - Controller Parameter Configuration; Parameter Categories and Settings; Refrigerant and Unit System Setup; Compressor and CRII Configuration

Bitzer ECOLITE Series
11 pages
Go to English
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
KQ-206-2 // PDF Download 9
Set parameters
1. Press F2 + F4 simultaneously ⇒ PAR
2. Press F4 ⇒ CNF
3. Use F1/F3 for choosing:
CNF
CPR
FAN
COR
For each of these menu items, press F4 to confirm and again use F1/F3 for choosing the parameters of each sub-
menu (see below).
Press F4 to confirm each of these settings. Press F2 one or several times to return to main menu.
CNF: Settings for unit
!
!
NOTICE
For A2L application, see Operating Instructions
KB-206
!
ERT Refrigerant 0 = R404A
4 = R134a
5 = R407C
8 = R507A
9 = R407A
11 = R407F
12 = R450A
14 = R448A
15 = R513A
17 = R449A
18 = R1234yf
19 = R1234ze
21 = R454C
23 = R455A
ECM CRII configur-
ation
0 = No CRII
1 = 2-cylinder compressor with
CRII
2 = 4-cylinder compressor with 1
x CRII
3 = 4-cylinder compressor with 2
x CRII
OSP Operation
mode
2 = Room temperature control
(also set SP1 at 10K below SP4,
see below!)
4 = Evaporating temperature
control (see SP1 below!)
SMU Unit system 0 = SI (bar / °C)
1 = Imperial (PSI / °F)
CPR: Settings for compressor and CRII

Related product manuals