Application limits
See BITZER Software or respective
brochure / Applications Manual:
SP-100 / SH-100: HS.53 .. HS.74
SP-110 / SH-110: HS.85
SP-500 / SH-500: OS.53 & OS.74
SP-510 / SH-510: OS.85
Cycling rate
Attention!
Danger of severe compressor
damage!
The following requirements
must be ensured by the
control logic:
Maximum cycling rate
6 to 8 starts per hour!
5 minutes minimum operating time
desired!
!
!
Limites d'application
Voir BITZER Software ou spécifique pros-
pectus / manuel de mise en œuvre:
SP-100 / SH-100: HS.53 .. HS.74
SP-110 / SH-110: HS.85
SP-500 / SH-500: OS.53 & OS.74
SP-510 / SH-510: OS.85
Fréquence d'enclenchements
Attention !
Risque de défaillance du compres-
seur !
Les conditions suivantes doivent
absolument assurées par la logique
de commande:
Fréquence maximale d'enclenche-
ments
6 à 8 démarrages par heure !
Durée de marche à atteindre au mini-
mum: 5 minutes !
!
!
Einsatzgrenzen
Siehe BITZER Software oder jeweili-
ger Prospekt / Projek tierungs-
Handbuch:
SP-100 / SH-100: HS.53 .. HS.74
SP-110 / SH-110: HS.85
SP-500 / SH-500: OS.53 & OS.74
SP-510 / SH-510: OS.85
Schalthäufigkeit
Achtung!
Gefahr von Verdichterausfall!
Unbedingt folgende Anforderun -
gen durch entsprechende
Steuerungslogik einhalten:
Maximale Schalthäufigkeit
6 bis 8 Starts pro Stunde!
Anzustrebende Mindestlaufzeit
5 Minuten!
!
!
SW-110-2