MBS0709E, MBS12E
www.blaupunkt.com
18
2. Turn on the machine, adjust it to low-wind ventilation mode, and maintain this state
until the drainage pipe becomes dry, so as to keep the inside of the body in a dry state
and prevent it from mildewing.
3. Turn o the machine, unplug the power plug, and wrap the power cord around the
wrapping post; install the water plug and the drainage cover.
4. Remove the exhaust pipe and keep it properly.
5. Cover the air conditioning with a plastic bag. Put the air conditioning in a dry place, keep
it out of the reach of children, and take dust control measures.
6. Remove batteries of the remote control and keep them properly.
Note:
Ensure that the body is placed in a dry place and keep all machine components properly.
IX Troubleshooting
1. Information on servicing
1) Checks to the area
Prior to beginning work on systems containing ammable refrigerants, safety checks are nec-
essary to ensure that the risk of ignition is minimised. For repair to the refrigerating system,
the following precautions shall be complied with prior to conducting work on the system.
2) Work procedure
Work shall be undertaken under a controlled procedure so as to minimise the risk of a am-
mable gas or vapour being present while the work is being performed.
3) General work area
All maintenance sta and others working in the local area shall be instructed on the nature
of work being carried out. Work in conned spaces shall be avoided. The area around the
workspace shall be sectioned o. Ensure that the conditions within the area have been made
safe by control of ammable material.
4) Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during work,
to ensure the technician is aware of potentially ammable atmospheres. Ensure that the
leak detection equipment being used is suitable for use with ammable refrigerants, i.e.
non-sparking, adequately sealed or intrinsically safe.
5) Presence of re extinguisher
If any hot work is to be conducted on the refrigeration equipment or any associated parts,
appropriate re extinguishing equipment shall be available to hand. Have a dry powder or
CO2 re extinguisher adjacent to the charging area.