INSTRUCTIONS MANUAL FOR BOILERS MODELS:
1460040EN
Updated 04/2009
PACK-P AR 93 PACK-P AR 810
PACK-P AR 105 PACK-P AR 930
PACK-P AR 150 PACK-P AR 1045
PACK-P AR 190 PACK-P AR 1100
PACK-P AR 230 PACK-P AR 1250
PACK-P AR 290 PACK-P AR 1600
PACK-P AR 345 PACK-P AR 1800
PACK-P AR 405 PACK-P AR 2000
PACK-P AR 465 PACK-P AR 2500
PACK-P AR 520 PACK P-AR 3000
PACK-P AR 580 PACK P-AR 3500
PACK P-AR 695
0085

Questions and Answers

  • A
    Angela ThomasAug 17, 2025
    How to fix a BLOWTHERM PACK-P AR 2000 Boiler when the burner does not turn on?
    • C
      Craig McleanAug 17, 2025
      If the burner of your BLOWTHERM Boiler does not turn on, you should first check the electrical connections and ensure they are properly connected. Next, verify that there is a regular fuel supply reaching the burner. After that, inspect the fuel supply system for integrity and cleanliness, making sure no air is present. Also, confirm that ignition sparks are forming regularly and that the burner appliance is functioning correctly. Check the boiler safety thermostat, ensuring it hasn't intervened and requires a manual reset. Finally, check the calibration of the environment thermostat.
  • T
    Timothy TateAug 19, 2025
    What to do if my BLOWTHERM PACK-P AR 2000 reaches temperature but the heating system is cold?
    • H
      Harold AshleyAug 19, 2025
      If your BLOWTHERM Boiler reaches the appropriate temperature but the heating system remains cold, you should check that there is no air in the system and that the circulation pumps are functioning correctly. In addition, verify the ambience thermostat setting to ensure it is properly configured.
  • M
    Margaret HillAug 22, 2025
    Why does my BLOWTHERM Boiler get easily covered with soot?
    • M
      Michael RobinsonAug 22, 2025
      If your BLOWTHERM Boiler gets easily covered with soot, start by checking the burner regulation through smoke analysis. Then, examine the fuel quality to ensure it meets the required standards. Also, check the flue for any clogging and ensure the burner air intake is clean and free from dust.
  • C
    Christopher ManningAug 26, 2025
    What to do if BLOWTHERM PACK-P AR 2000 Boiler burner turns on then immediately off?
    • B
      Brittany WatersAug 26, 2025
      If the burner turns on well but then turns off immediately after in your BLOWTHERM Boiler, you should check the pilot flame, the air calibration, and ensure that the burner appliance is working correctly.
  • J
    Jacob WrightAug 28, 2025
    Why do I smell gas from my BLOWTHERM PACK-P AR 2000 Boiler?
    • I
      Ivan LozanoAug 28, 2025
      If you smell gas or un-combusted products from your BLOWTHERM Boiler, it's important to check the seal of the fuel supply system, especially if it uses gas fuel. Also, check the hermetic seal of the smoke circuit, including the door, smoke box, and boiler/flue connection.
  • C
    colecandiceAug 30, 2025
    Why does my BLOWTHERM PACK-P AR 2000 Boiler not reach set temperature?
    • R
      Roberto RogersAug 30, 2025
      If your BLOWTHERM Boiler does not reach the set temperature, you should ensure that both the smoke side and water side of the boiler are clean. Check the combination, regulation, and overall performance of the burner. Verify the regulation of the pressure switches and confirm they are working correctly. Also, inspect the position of the thermostat gauges and ensure the boiler capacity is appropriate for the plant.
  • S
    Samuel WhiteSep 2, 2025
    What causes the safety valve of the BLOWTHERM Boiler to intervene often?
    • E
      Eric WareSep 2, 2025
      If the safety valve of your BLOWTHERM Boiler intervenes often, you should check the system loading pressure. Also, check the efficiency of the expansion vessel and the calibration of the valve itself.
  • C
    Carolyn AndersenSep 4, 2025
    How to troubleshoot a BLOWTHERM PACK-P AR 2000 with difficult burner adjustment and no output?
    • D
      Douglas JohnsonSep 4, 2025
      If the burner of your BLOWTHERM Boiler is difficult to adjust or has no output, you should check the burner, boiler, boiler/flue pipes, and flue for cleanliness. Also, verify the hermetic seal of the smoke circuit, including the door, smoke box, and boiler/flue connection. Ensure the fuel supply is flowing regularly and verify the effective power of the burner. Finally, check for the presence of scale and consider carrying out a chemical washing.
  • T
    thernandezSep 7, 2025
    Why is there water on the floor near the smoke box of my BLOWTHERM PACK-P AR 2000?
    • H
      heather57Sep 8, 2025
      If you find water on the floor near the smoke box (condensate) of your BLOWTHERM Boiler, verify that the probes have been positioned correctly. Ensure the boiler thermostat has been regulated correctly (between 60 and 90°C) and is functioning well. Also, verify that the discharge in the fumes box is connected with a gathering ground. Check that the anti-condensate pump and its regulation (if present) are working correctly. Finally, check that the temperature of the return water of the plant is not less than 50°C.
  • M
    Maria BrowningSep 12, 2025
    What causes the safety thermostat to intervene in a BLOWTHERM PACK-P AR 2000 Boiler?
    • M
      Mr. David SmithSep 12, 2025
      If the safety thermostat intervenes in your BLOWTHERM Boiler, check the electric wires. Also, check that the gauges bulbs are positioned correctly and all thermostats are working correctly.

Summary

General Information

1.1 General Warnings

Essential safety guidelines and precautions for boiler operation and handling.

1.3 Safety Rules

Critical safety rules for users to prevent hazards and ensure safe operation.

User

2.1 Start-up Operations

Procedure for starting the boiler, including user-initiated restarts.

Installation

3.2 Installation - Boiler Room

Requirements and considerations for installing the boiler in a dedicated room.

3.3 Discharge of Combustion Products

Guidelines for correct burner/boiler/flue coupling and flue system requirements.

3.4 Hydraulic Connection

Recommendations for connecting the boiler to the heating system hydraulics.

3.9 Electrical System

Requirements for the electrical system installation and safety compliance.

3.11 Fuel Supply

Regulations and procedures for the fuel supply line installation.

3.15 Preliminary Operations Before First Start-up

Checklist of essential checks before the initial boiler start-up.

3.16 First Start Up

Procedure for powering on the boiler for the first time and initiating the ignition cycle.

3.17 First Start Up and Further Checks

Steps for testing and verifying the boiler's operation after the initial start-up.

Service

4.6 Troubleshooting

Common faults, their causes, and recommended solutions for diagnosing issues.

BLOWTHERM PACK-P AR 2000 Specifications

General IconGeneral
BrandBLOWTHERM
ModelPACK-P AR 2000
CategoryBoiler