INSTRUCTIONS MANUAL FOR BOILERS MODELS:
1460040EN
Updated 04/2009
PACK-P AR 93 PACK-P AR 810
PACK-P AR 105 PACK-P AR 930
PACK-P AR 150 PACK-P AR 1045
PACK-P AR 190 PACK-P AR 1100
PACK-P AR 230 PACK-P AR 1250
PACK-P AR 290 PACK-P AR 1600
PACK-P AR 345 PACK-P AR 1800
PACK-P AR 405 PACK-P AR 2000
PACK-P AR 465 PACK-P AR 2500
PACK-P AR 520 PACK P-AR 3000
PACK-P AR 580 PACK P-AR 3500
PACK P-AR 695
0085

Questions and Answers

  • B
    Brittany WilsonAug 16, 2025
    How to fix a BLOWTHERM PACK-P AR 345 Boiler when the burner does not turn on?
    • C
      Christopher JuarezAug 16, 2025
      If the burner of your BLOWTHERM Boiler does not turn on, you should first check the electrical connections and ensure they are properly connected. Next, verify that there is a regular fuel supply reaching the burner. After that, inspect the fuel supply system for integrity and cleanliness, making sure no air is present. Also, confirm that ignition sparks are forming regularly and that the burner appliance is functioning correctly. Check the boiler safety thermostat, ensuring it hasn't intervened and requires a manual reset. Finally, check the calibration of the environment thermostat.
  • A
    amy60Aug 22, 2025
    Why does my BLOWTHERM PACK-P AR 345 Boiler get easily covered with soot?
    • C
      Cynthia ThompsonAug 22, 2025
      If your BLOWTHERM Boiler gets easily covered with soot, start by checking the burner regulation through smoke analysis. Then, examine the fuel quality to ensure it meets the required standards. Also, check the flue for any clogging and ensure the burner air intake is clean and free from dust.
  • M
    Manuel CamposAug 25, 2025
    What to do if BLOWTHERM Boiler burner turns on then immediately off?
    • M
      Mark NicholsonAug 26, 2025
      If the burner turns on well but then turns off immediately after in your BLOWTHERM Boiler, you should check the pilot flame, the air calibration, and ensure that the burner appliance is working correctly.
  • L
    Laura IbarraAug 27, 2025
    Why do I smell gas from my BLOWTHERM PACK-P AR 345 Boiler?
    • M
      Michael HansenAug 27, 2025
      If you smell gas or un-combusted products from your BLOWTHERM Boiler, it's important to check the seal of the fuel supply system, especially if it uses gas fuel. Also, check the hermetic seal of the smoke circuit, including the door, smoke box, and boiler/flue connection.
  • E
    Elizabeth RamosAug 30, 2025
    Why does my BLOWTHERM PACK-P AR 345 not reach set temperature?
    • K
      Kevin HaydenAug 30, 2025
      If your BLOWTHERM Boiler does not reach the set temperature, you should ensure that both the smoke side and water side of the boiler are clean. Check the combination, regulation, and overall performance of the burner. Verify the regulation of the pressure switches and confirm they are working correctly. Also, inspect the position of the thermostat gauges and ensure the boiler capacity is appropriate for the plant.
  • P
    Patrick BaxterSep 2, 2025
    What causes the safety valve of the BLOWTHERM PACK-P AR 345 to intervene often?
    • F
      Frank SmithSep 2, 2025
      If the safety valve of your BLOWTHERM Boiler intervenes often, you should check the system loading pressure. Also, check the efficiency of the expansion vessel and the calibration of the valve itself.
  • N
    Nathan WoodsSep 5, 2025
    How to troubleshoot a BLOWTHERM PACK-P AR 345 with difficult burner adjustment and no output?
    • L
      Lauren RobertsSep 5, 2025
      If the burner of your BLOWTHERM Boiler is difficult to adjust or has no output, you should check the burner, boiler, boiler/flue pipes, and flue for cleanliness. Also, verify the hermetic seal of the smoke circuit, including the door, smoke box, and boiler/flue connection. Ensure the fuel supply is flowing regularly and verify the effective power of the burner. Finally, check for the presence of scale and consider carrying out a chemical washing.
  • G
    gsloanSep 7, 2025
    Why is there water on the floor near the smoke box of my BLOWTHERM Boiler?
    • H
      hooperphilipSep 7, 2025
      If you find water on the floor near the smoke box (condensate) of your BLOWTHERM Boiler, verify that the probes have been positioned correctly. Ensure the boiler thermostat has been regulated correctly (between 60 and 90°C) and is functioning well. Also, verify that the discharge in the fumes box is connected with a gathering ground. Check that the anti-condensate pump and its regulation (if present) are working correctly. Finally, check that the temperature of the return water of the plant is not less than 50°C.
  • S
    Sandy BuckSep 10, 2025
    What causes the safety thermostat to intervene in a BLOWTHERM PACK-P AR 345?
    • L
      Lindsey HammondSep 12, 2025
      If the safety thermostat intervenes in your BLOWTHERM Boiler, check the electric wires. Also, check that the gauges bulbs are positioned correctly and all thermostats are working correctly.
  • P
    paula77Sep 10, 2025
    What to do if my BLOWTHERM PACK-P AR 345 reaches temperature but the heating system is cold?
    • D
      David CantrellSep 12, 2025
      If your BLOWTHERM Boiler reaches the appropriate temperature but the heating system remains cold, you should check that there is no air in the system and that the circulation pumps are functioning correctly. In addition, verify the ambience thermostat setting to ensure it is properly configured.

Summary

General Information

General Warnings and Safety Precautions

Essential safety guidelines and warnings for using the boiler safely.

Certification and Technical Specifications

Details on boiler certifications, dimensions, and technical features.

Electrical System Overview

Information on the standard instrument panel, electrical diagrams, and wiring.

User Operations

Boiler Start-Up and Shut-Down Procedures

Step-by-step instructions for starting and turning off the boiler.

Cleaning and Maintenance Guidelines

Procedures for cleaning the boiler and performing routine maintenance.

Product Receipt and Handling

Instructions on receiving and handling the boiler upon delivery.

Installation Procedures

Boiler Room Installation and Setup

Requirements for boiler room installation, ventilation, and positioning.

Combustion, Flue, and Hydraulic Systems

Guidance on combustion product discharge, flue connection, and hydraulic setup.

Fuel Supply and Burner Connection

Information on fuel types, supply lines, and burner connection procedures.

First Start-Up and Final Checks

Detailed steps for preliminary checks, first start-up, and subsequent testing.

Service and Maintenance

Service Center Warnings and Routine Maintenance

Mandatory maintenance, service warnings, and routine checks for optimal performance.

Boiler Cleaning and Post-Cleaning Checks

Instructions for cleaning the boiler and performing necessary checks afterwards.

Troubleshooting Common Boiler Faults

Descriptions of common faults and their recommended remedies.

Spare Parts and Warranty Information

List of recommended spare parts and details on the product warranty.

BLOWTHERM PACK-P AR 345 Specifications

General IconGeneral
BrandBLOWTHERM
ModelPACK-P AR 345
CategoryBoiler