READ AND FOLLOW ALL INSTRUCTIONS
⚫ Disconnect all AC power during installation.
⚫ Do not permit children to use this product.
⚫ A green-colored screw is located inside the wiring compartment,
against the back panel. To reduce the risk of electric shock, this
terminal must be connected grounded by connecting a continuous
copper wire, equivalent in size to the circuit conductors supplying
the equipment. Use the means provided in the electric supply
service panel to connect the terminal to the grounding.
⚫ Includes one bonding lug for US models (two for Canadian models)
located on the external surface. To reduce the risk of electric
shock, connect the local common bonding grid in the area of the
swimming pool, spa, or hot tub to these terminals with an insulated
or bare copper conductor not smaller than 8 AWG US/6 AWG
Canada.
⚫ All field-installed metal components such as rails, ladders, drains,
or other similar hardware located within 10 feet (3 meters) of the
pool, spa or hot tub shall be bonded to the equipment grounding
bus with copper conductors not smaller than 8 AWG US/ 6 AWG
Canada.