EasyManua.ls Logo

Bosch B20CS50 Series - Defrost Mode

Bosch B20CS50 Series
71 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11
1. Defrost Mode
INPUT CONTROL OBJECT
CONTENTS REMARKS
1. Defrosting Cycle
1. Comp
2. F-Fan
3. R-Fan
4. D-Heater
Pause
Fan-Delay
Heater
Defrosting
Heater
Defrosting
1) Comp, F-fan, R-fan : OFF
Defrost-Heater : ON
2) Time limit
30 seconds : Heater is ON regardless of D-sensor
temperature right after defrosting start
30 minutes : in case of D1- Error
80 minutes : in normal control state
3) If D-sensor 13, Heater Defrosting is OFF
Pause
Time : 7 minutes
Comp, F-fan, R-fan, Heater etc. : OFF
Fan-Delay
1) Time : 5 minutes
Comp : ON and F-fan, R-fan, Heater : OFF
4-2. Defrost Mode
2.The defrost mode start with the following conditions
1) Total operation time of comp. becomes : 6,8,10,………,12 hours.
Room Temperature 35 & Comp. operating rate 85%
Total door open time : 2 minutes
(Any door, F or R open time is over 2 minutes.)
Any error mode : R1, F1, D1, F3, RT/S, Door-switch etc.)
2) Defrosting mode starts unconditionally as long as total comp. work time is
12 hours, even if the above conditions 1) are not satisfied.
3) Defrosting mode starts immediately as long as total time of [comp. ON +
comp. OFF] is over 60 hours, even if the above 1) and 2) conditions are not
satisfied.
3. In providing initial power (or returning power failure)
If D-sensor temp. 3.5, defrosting mode starts .