Service Manual
Bosch Climate 5000 Series Ductless Air Conditioner / Heat Pump Multi Zone Outdoor Units (01.2023)
8.6.7 Outdoor fan speed malfunction (EC 07) Over current failure of
outdoor DC fan motor (EC 71)
Error Code EC 07/ EC 71
Malfunction decision conditions
When outdoor fan speed keeps too low (300RPM) or too high(2400RPM) for certain time, the unit will
stop and the LED will display the failure.
Supposed causes
f Improper / Incorrect Wiring
f Faulty Fan assembly
f Faulty Fan motor
f Outdoor PCB faulty
Table 37
Troubleshooting:
Figure 67
n
Power off, then restart the
unit 3 minutes later. Is it still
displaying the error code?
S
s
Shut off the power supply,
rotate the fan by hand. Does
it rotate properly?
The unit operates normally.
h
d
Find out the cause and
have it solved. For
example, check whether
the fan is blocked or the
screws which secure the
fan are ght.
Check the wiring of fan
motor. Are all the
connections good?
No
Yes
No
Correct the connections.No
Replace the fan motor
Yes
Yes
e
a
Replace the No
s
m
Check whether the outdoor PCB
is normal through index 1?
Yes
No
outdoor PCB