| 65
Service Manual
Bosch Climate 5000 Series Ductless Air Conditioner / Heat Pump Multi Zone Outdoor Units (01.2023)
Index 1:
1. DC fan motor(control chip is inside fan motor)
Power on and when the unit is in standby, measure the voltage of pin1-pin3,
pin3-pin4 in fan motor connector. If the value of the voltage is not in the range
showing in below table, the PCB must have problems and need to be replaced.
Figure 68
Figure 69
Vs
Vcc
Vsp
FG
DC motor voltage input and output
NO. Color Signal Voltage
1 Red Vs/Vm 200~380V
2 --- --- ---
3 Black GND 0V
4 White Vcc 13.5~16.5V
5 Yellow Vsp 0~6.5V
6 Blue FG 13.5~16.5V
Table 38