EasyManua.ls Logo

Bosch Buderus Logamatic 5000 Series - Power-controlled heat request via Modbus TCP;IP from and including version 1.3.X; Information on Heat request via Modbus and Internal heat request parameters

Bosch Buderus Logamatic 5000 Series
33 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User Documentation
14|33
© All rights with Robert Bosch GmbH, also for the case of protected rights applications
EN_User_documentation_Instructions_for_controlling_the_Logamatic_5000_controller_series_via_Modbus_TCP_I
P_20210203.docx | 10.02.2021
Note:
With the values from the above example, a temperature-controlled heat re-
quest with X °C, which is to work as a lead boiler, is sent to a boiler. For a
system with FM-CM, the guide boiler function must be enabled.
X in °C corresponds to your desired flow temperature.
2.6.2 Power-controlled heat request via Modbus TCP/IP from and in-
cluding version 1.3.X
To be able to send a power request via Modbus, you must first configure the control-
ler accordingly (see chapter "Information on parameters 'Heat request via Modbus'
and 'Internal heat request'").
Then you can write to the following Modbus registers:
Register
Value of Register
Operation Mode
(Holding Register 402)
1
Flow Temperature Set point
(Holding Register 400)
X in %
Leading Boiler
(Holding Register 405; Bit
0
)
1
Temperature controlled operation
(Holding Register 405; Bit
2
)
0
Power controlled operation
(Holding Register 405; Bit
3
)
1
Note:
With the values from the above example, a power-controlled heat request
with X %, which is to work as a lead boiler, is sent to a boiler. In the case of a
system with FM-CM, it is mandatory to enable the guide boiler function.
You can only use the output-guided control if you have deactivated the inter-
nal heat request.
X in % corresponds to your desired output..
2.6.3 Information on 'Heat request via Modbus' and 'Internal heat re-
quest' parameters
You can use the following parameters of the controller to define how a heat or power
request can be generated at the controller. The parameters for configuring the be-
havior can be found in the Service menu > Heat generation > Strategy data > Basic
settings. Depending on the parameterization, this may have an effect on the control.

Table of Contents

Related product manuals