Communication Systems | LBB 1990/00 Plena Voice Alarm Controller
The Plena Voice Alarm Controller is the heart of the voice
alarm system. It is the basis of the Plena Voice Alarm
System, and has all the essential functionality for
compliance with the IEC 60849 standard, including full
system supervision, loudspeaker line impedance
supervision, a supervised emergency microphone on the
front panel and a supervised message manager.
The messages can be merged to allow even more flexible
use of pre-recorded announcements and evacuation
messages. The controller can be used as a stand-alone
system with up to 6 zones, or expanded to up to
60 zones using additional 6-zone routers. Up to 8 call
stations can be connected. Interconnections are made
using standard RJ45 connectors and shielded CAT-5
cable.
A built-in 240 W amplifier provides the power for the
emergency call channel and BGM. Additional Plena
Amplifiers can be added to provide two-channel
operation, or for additional power if the total power
requirement exceeds 240 W (maximum 480 W per 6
zones). All amplifiers are supervised. The audio output
uses standard analog audio 100 V line switching for full
compatibility with the Plena family of public address
equipment and Bosch EVAC-compliant loudspeakers.
The system is configured using DIP switches for basic
functionality and a PC for more advanced functions.
Functions
The controller has two BGM source inputs and a mic/line
input with configurable priority, speech filter, phantom
power and selectable VOX activation. A total of 16
priority levels can be specified for microphone, call
stations and trigger inputs for optimum system
flexibility.
The powerful 240 W output section has six transformer-
isolated 100 V constant voltage outputs for driving 100 V
loudspeakers in six separate zones. The 100 V-technique
reduces line losses on longer distances and allows for
easy parallel connection of multiple loudspeakers. All
zones may be individually selected from the front panel,
and the BGM output level in each zone can be
individually set in 6 steps. The BGM output is connected
to the 70 V line, so it is possible to connect a total load
of 480 Watts in a two-channel system combined with a
480 Watt booster.
The output of the booster is also available as a separate
output on 100 V and 70 V. A separate 100 V Call Only
output is provided for addressing an area where BGM is
not required but where priority announcements are. Six
configurable Volume Override output contacts are
available for overriding local volume controls during
priority calls. A LED VU-meter monitors the output.
Up to 255 messages can be stored in the internal
16 MB flash ROM, without a need for battery backup.
LBB 1990/00 Plena Voice Alarm Controller
Heart of the Plena Voice Alarm System
Compliant with standards for emergency sound
systems (IEC60849)
6-zone system controller
Built-in 240 W booster amplifier
12 Business and emergency control inputs and
outputs
www.boschsecurity.com
Question and Answer IconNeed help?

Do you have a question about the Bosch LBB 1990/00 and is the answer not in the manual?

Bosch LBB 1990/00 Specifications

General IconGeneral
BrandBosch
ModelLBB 1990/00
CategoryController
LanguageEnglish

Summary

Plena Voice Alarm Controller Overview

Key Features

Highlights compliance with IEC60849, 6-zone control, built-in 240W booster, and 12 I/O capabilities.

Functions

Details controller inputs, priority levels, mic/call station flexibility, and trigger inputs for system control.

Technical Specifications

Electrical

Specifies mains voltage, power consumption, output power, and current ratings for the controller.

Performance

Details frequency response, distortion, and audio control parameters for the voice alarm system.

Inputs Mic/Line

Describes input types, sensitivity, S/N ratio, headroom, speech filter, and phantom power.

BGM and PC Call Station

Covers input type, level, impedance, S/N ratio, headroom, trigger inputs, and activation methods.

Outputs

Details tape output, nominal level, impedance, loudspeaker outputs, and volume override types.

Output Contacts

Lists contact types, ratings, and specific relays for emergency, call, fault, and general purposes.

Environmental

Specifies operating and storage temperature, relative humidity, and acoustic noise level.

Messages

Details data format, supported sample rates, frequency response, distortion, memory, and recording time.