Installation instructions
3 Installation instructions
3.1 Specialized tools
The following specialized tools may be required for
installation:
• Manometer
• Multi-meter
• Combustion Gas Analyzer.
3.2 Introduction
Please follow these instructions. Failure to follow
instructions may result in:
B Damage or injury.
B Improper operation.
B Loss of warranty.
3.3 Venting
3.3.1 Vent material
All combustion air and vent pipe materials and fittings
must comply with the following:
For specific questions concerning vent material,
specifications, usage or installation, please
contact the vent manufacturer directly.
All vent connections must be glued, except for the
exhaust accessory (see section 3.3.4) which is
screwed into place on the top of the appliance. Slide
the vent pipe into the exhaust accessory. The exhaust
pipe must be properly supported and must be pitched
a minimum of a ¼ inch per foot back to the appliance.
This allows the condensate to drain properly.
An optional concentric vent/air intake termination can
be used for the installation of a vertical or horizontal
venting system. (see Fig. 8).
The concentric vent/air intake body can be ordered
from your local wholesaler. (Part# 196016).
The appliance can also be installed with separate air
intake and exhaust piping (see Fig. 11, Fig. 18 and Fig.
19, page 18).
Warning: The water heater must be
installed by a qualified installer in
accordance with these instructions. If
improperly installed, a hazardous condition
such as explosion or carbon monoxide
poisoning could result. Bosch
Thermotechnology Corp. is not
responsible for improperly installed
appliances.
Common installation practice is to
first determine the venting/
combustion air point of termination,
then design the piping layout back to
the heater.
Warning:
B Do not reduce the exhaust or
combustion air vent pipe sizes.
B Do not common vent with any other
vented appliance or stove.
B Do not use Type-B vent as the actual
exhaust vent system for the appliance.
Warning: Failure to vent the exhaust
gases to the outside (see Table 2 for
proper material) may result in
dangerous flue gases filling the
structure in which it is installed.
Warning: In areas where outside
temperatures routinely come close to
freezing, sealed combustion operation
is required. Concentric termination or
separate terminations for combustion
and vent, must be installed on the same
wall or roof surface; however, never
facing the direction of prevailing winds.
Failure to do so may result in heat
exchanger freezing and bursting. This
failure is not covered under the
manufacturer's warranty.
Warning: Protect the exhaust and inlet
from leaves and debris by installing a
screen on the end of the terminator.
¼" mesh minimum opening
recommended on screen.
Item Material United States Canada
Vent or
air pipe
and
fitting
PVC schedule 40 ANSI/ASTM D1785
CSA or ULC
certified only
(ULC-S636)
PVC-DWV ANSI/ASTM D2665
CPVC schedule 40 ANSI/ASTM F441
ABS-DWV schedule 40 ANSI/ASTM D2661
Pipe
cement /
primer
PVC ANSI/ASTM D2564
CPVC ANSI/ASTM F493
ABS ANSI/ASTM D2235
Table 2 Approved vent material
Do not use cellular foam core pipe.