EasyManua.ls Logo

Bosch F220 Series - Base Specifications; Detector Specifications; Electrical Supervision

Bosch F220 Series
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
F220 Series Detectors with F220-B6/C/E/R Bases General Information | en 9
Bosch Security Systems, Inc. Installation Manual 4998138694 -04 | 2007.01
2.3.2 Base Specifications
2.3.3 Detector Specifications
2.4 Electrical Supervision
When the F220-B6 Series Bases are wired according to the
instructions in this document, the control panel initiates a
trouble signal when a detector is removed from its base,
Alarm Current (only base current, detector current excluded)
F220-B6: Two-wire base; no base current
F220-B6C: 31 mA at 12 VDC
35 mA at 24 VDC
40 mA maximum at 30 VDC
F220-B6E: 25 mA at 12 VDC
30 mA at 24 VDC
34 mA maximum at 30 VDC
F220-B6R: 13.5 mA at 12 VDC
16.5 mA at 24 VDC
19 mA maximum at 30 VDC
Standby Current
F220-B6/C/R: No current draw in standby
F220-B6E: 16 mA maximum at 30 VDC
Voltage
F220-B6 (two-wire): 8.5 VDC to 32.0 VDC
F220-B6C/E/R (four-wire): 10.0 VDC to 30.0 VDC
Table 2.4 F220-B6 Series Base Specifications
Current
Alarm: 20 mA minimum at 8.5 VDC
35 mA maximum at 32 VDC
Standby: 0.12 mA maximum
Startup: 0.12 mA maximum
Powerup Time 22 second maximum
Rate of Rise
F220-135: 15°F/min (9°C/min) or greater
Voltage
Operating: 8.5 VDC to 32.0 VDC
RMS Ripple: 25% of DC input
Table 2.5 F220 Series Detector Heads Specifications