4 en | Safety Smoke detector POPIT base
2022.09 | 01 | F.01U.396.537 Bosch Security Systems B.V.
1 Safety
Notice!
NFPA
Installation must be carried out by trained and authorized
personnel.
Notice!
Make sure the volume of the electrical box you use is adequate
to accommodate the number and size of conductors as
specified by the National Electrical Code (NEC) or any local
regulations having jurisdiction.
2 Overview
These instructions cover the installation of the Addressable
Detector POPIT bases in an addressable system.
This device with built-in POPIT, provides individual addresses on
the G Series control panel POPEX bus. These bases accept the
FCP-350 Series Photoelectric Smoke Detector and FCH-350-135
Heat Detector Heads.
Notice!
Heat detector head voltage compatibility
The FAH-350-135 Heat Detector Heads can only be used at 24
V.
Notice!
FAH-350-190 high temperature
The FAH-350-190 Heat Detector head should not be used with
the FAA-350-B6 POPIT base due to a higher temperature
threshold from the FAH-350-190 detector head. The
temperature range is too high for the electronics in the
FAA-350-B6 POPIT base and may not signal an alarm/trouble
event.