8 en | Base POPIT addresses Smoke detector POPIT base
2022.09 | 01 | F.01U.396.537 Bosch Security Systems B.V.
4 Base POPIT addresses
Each detector base has a specific address point that is
determined by setting the seven DIP switches on the detector’s
base. The base address number does not depend on the base
location in the circuit.
If adding the base to an FACP version B1 or earlier, set switch 1
to ON and leave all other switches off.
DIP switch key:
ON = DIP switch in the up position
OFF = DIP switch in the down position
Refer to the following table for DIP switch 0 settings and the
following address switch table for DIP switch configuration
settings for ZONEX and ZONEX2.
Control panel DIP switch 0 setting
D7212B1
D8112
D9112B1
Leave switch 0 ON.