Installation Instructions Linear Smoke Detector Fireray 50/100RV
ST/PMF/zab
610-F.01U.002.706 / A2.en
Page 11 of 14
6. Appendices
6.1. Installation protocol
Installation company:
Type of object:
Installation location:
Installation date:
Total number of all linear detectors:
Detector version: Fireray 50RV
Fireray 100RV
Detector – reflector distance: _________ m
Distance of the detector axes to one
another
_________ m
Mounting height _________ m
Mounting surface (e.g. masonry/rein-
forced concrete/steel beams/wood/etc.)
Serial number(s)
Reflector size: 1 x (10 x 10 cm)
4 x (20 x 20 cm)
Supply voltage: _________ V
Correct mechanical adjustment
of transmitter
(when gentle pressure is applied to the
detector housing from the left/right/top/
bottom, the yellow LED lights up initially):
yes no
Alarm triggered with absorption film
35% - 50% tested:
yes no
Fault triggered by disruption of IR
beam tested:
yes no
DIP switch settings:
on
off
1234
Comments (environmental conditions, e.g. dust, humidity, temperature etc.)
Installation tested on: ____________ by: __________________________