EasyManua.ls Logo

Bosch FW 100 - Solar Sys Parameters; INSTALLER SETTINGS: Fault History

Bosch FW 100
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 720 645 349 (2010/09)
Menu settings INSTALLER SETTINGS (contractors only) | 45
8.1.4 INSTALLER SETTINGS: Solar sys parameters
8.1.5 INSTALLER SETTINGS: Fault history
Menu structure
Solar sys parameters
Factory
setting
Setting range
Personal
setting
Description
from page
1. Standard system
52
SP: ON temperature
difference
8 K 3 K ... 20 K
(not lower than "SP: OFF
temperature difference" +1 K)
K
SP: OFF temperature
difference
4 K 2 K ... 19 K
(not higher than "SP: ON
temperature difference" – 1 K)
K
T2: Max. solar cylinder
temperature
60 °C 15 °C ... 95 °C °C
Maximum collector
temperature
130 °C 90 °C ... 135 °C °C
SP: Collector grp 1 pump
mode
Auto Auto | Manual On | Manual Off
PE: Therm disinfect pump mode Auto Auto | Manual On | Manual Off 53
Solar optimisation
53
Collector group 1 area 0.0 m
2
0.0 m
2
... 150.0 m
2
m
2
Collector group 1 type Flat plate
collector
Flat plate collector | Vac tube
collector
Climate zone 90 0 ... 255
Optimizing influence DHW 0 K 0 K (= function off) ... 20 K K
CH circuit optimizing
influence
0.0 K 0.0 K (= function off) ... 5.0 K K
Run solar system No No | Yes 55
Menu structure
Fault history
Factory
setting
Setting range
Personal
setting
Description
from page
01.01.2010
16:11
Fault EA
(example for last fault)
– –
55
25.09.2010
18:45
FAULT 44 - IPM IDENT. 10
(up to a maximum of 19
previous faults)
– –

Table of Contents

Related product manuals