6 720 817 281 (2017/05)Greentherm 9800 SEO 160/199 | SECO 199
Troubleshooting | 35
Record the L1 gas adjustment value in table 16, when the
display starts blinking (as sign of confirmation).
Press button to finish the L1 gas adjust (U1).
▶Press or until P1 appears.
Press the button .
Display with indication "E".
Press the button until the display shows "A1".
▶Press .
The appliance is now in the position for adjustment of the
maximum air flow.
Press the buttons or until the CO
2
analyzer
shows the value indicated in tab. 17.
Press the button for 3 seconds.
The value flashes as a sign of confirmation.
Press the button to come out of this function.
Display with indication "A1".
Close the hot water tap.
Press until the display shows "E".
Press the button .
Display with indication P1.
The adjustment of the maximum gas flow is finalized.
10.11.3Adjusting the minimum flow (Parameter P2)
Press until the display shows "P2".
Appliance will ramp down to low fire and the water flow
should decrease. Wait a few minutes until stabilize.
▶Press or until U2 appears.
Press the button .
The appliance will start the auto adjustment of the
minimum gas flow.
Record the L2 gas adjustment value in table 16, when the
display starts blinking (as sign of confirmation).
Press button to finnish the L2 gas adjust (U2).
▶Press or until P2 appears.
Press the button .
Display with indication "E".
Press the button until the display shows "A2".
▶Press .
The appliance is now in the position for adjustment of the
maximum air flow.
Press the buttons or until the CO
2
analyzer
shows the value indicated in tab. 17.
Press the button for 3 seconds.
The value flashes as a sign of confirmation.
Press the button to come out of this function.
Display with indication "A2".
Close the hot water tap.
Press until the display shows "E".
Press the button .
Display with indication P2.
The adjustment of the maximum gas flow is finalized.
Press simultaneously buttons , and for 3
seconds.
Display with indication of temperature selected.
Remove CO
2
analyzer probe from the appliance.
The auto adjust process takes several
minutes.
Do not interfere with the appliance
during the auto adjustment process.
After adjusting parameter P1 and to avoid
damaging the CO
2
analyzer remove and
allow the unit to operate in P2 mode for 1 or
2 minutes before measuring and adjusting
parameter P2.
The auto adjust process takes several
minutes.
Do not interfere with the appliance
during the auto adjustment process.
Readings Gas parameter Air Adjustment
Max.
Power
L1 value:_____ A1 value:_____ CO
2
value:_____
Min.
Power
L2 value:_____ A2 value:_____ CO
2
value:_____
Table 16