6 720 817 281 (2017/05) Greentherm 9800 SEO 160/199 | SECO 199
40 | Problem solving
CE Flue blockage detected during operation due to
excessive pressure on the siphon.
Reset error (press and hold on/off button for 3
seconds).
If the problem persists:
Check air openings and exhaust opening for
obstructions and reset the error.
Perform gas and air tuning ( section 10.11).
1)
CF Flue blockage detected during operation due to
insufficient combustion air.
Reset error (press and hold on/off button for 3
seconds).
If the problem persists:
Check air openings and exhaust opening for
obstructions and reset the error.
Perform gas and air tuning ( section 10.11).
1)
E0 Electronic control unit internal error. Reset error (press and hold on/off button for 3
seconds).
If the problem persists:
Replace electronic control unit.
1)
E1 Hot water temperature above 194 °F.
Appliance burner cut off to prevent scalding and
reactivation after cooling down.
Disconnect the appliance and purge hydraulic
circuit to remove air.
If the problem persists:
Reduce setpoint temperature to minimize
temperature instabilities.
E3 Flue gases temperature above 194 °F or 2 minutes
above 145 °F.
Appliance burner cut off to prevent overheating.
Descale appliance ( section 9.3).
1)
Reset error (press and hold on/off button for 3
seconds).
If the problem persists:
Check sensor resistance [15] (section 13) and
replace the sensor if it is not according to
specification.
1)2)
E4 Air temperature inside cabinet above 176 °F or 2
minutes above 158 °F.
Appliance burner cut off to prevent overheating.
Check for flue gas leakage inside the cabinet
1)
Reset error (press and hold on/off button for 3
seconds).
If the problem persists:
Check sensor resistance [18] (section 13) and
replace the sensor if it is not according to
specification.
1)
2)
E5 Condensing unit flue gases temperature above
428 °F or 2 minutes above 392 °F.
Appliance burner cut off to prevent overheating.
Descale appliance ( section 9.3).
1)
Reset error (press and hold on/off button for 3
seconds).
If the problem persists:
Check sensor resistance [16] (section 13) and
replace the sensor if it is not according to
specification.
1)
2)
E7 Electronic control unit internal error. Reset error (press and hold on/off button for 3
seconds).
If the problem persists:
Replace electronic control unit.
1)
Display Description Solution
Table 20