6720892984 (2019/02) US SSB
50 | Service reminder
C.2 Settings stored in 905MN controller
Menu item Sub item / Parameter Range Default Value Units User Level
Boiler
Parameters
(1) CH Mode 0..5 0 2: Installer
(3) CH Setpoint 30...90 (86...194) 60 (140) °C (°F) 1: User
(109) Calc. Setp. Offset Off, -10...10 (Off, -18...18) 0 °C (°F) 2: Installer
(110) CH Min Setpoint 20...50 (68...122) 20 (68) °C (°F) 2: Installer
(111) CH Max Setpoint 50...90 (122...194) 50 (122) °C (°F) 2: Installer
(5) Boiler Pump Overrun 0..900 30 Sec. 2: Installer
(6) Flue Temp Limit 10...120 (50...248) 100 (212) °C (°F) 3: Factory
(7) CH Hysteresis Up 0...20 (0...36) 20 (36) °C (°F) 2: Installer
(112) CH Hysteresis Down 0...20 (0...36) 5 (9) °C (°F) 2: Installer
(9) Anti Cycle Period 10..900 180 Sec. 2: Installer
(10) Anti Cycle Temp Diff 0...20 (0...36) 16 (29) °C (°F) 2: Installer
(12) Hx Diff ΔT Maximum 10...60 (18...108) 40 (72) °C (°F) 3: Factory
(13) Hx Diff Max Wait Time 10..250 10 Sec. 3: Factory
(14) Max Power CH 50..100 100 % 2: Installer
(15) Min Power CH 1..30 1 % 2: Installer
(16) CH PID P 0..1275 100 3: Factory
(17) CH PID I 0..1275 250 3: Factory
(18) CH PID D 0..1275 0 3: Factory
(19) Design Supply Temp 30...90 (86...194) 90 (194) °C (°F) 1: User
(20) Design Outdoor Temp -25...25 (-13...77) -5 (23) °C (°F) 1: User
(21) Baseline Supply Temp 30...90 (86...194) 40 (104) °C (°F) 2: Installer
(22) Baseline Outdoor Temp 0...30 (32...86) 20 (68) °C (°F) 2: Installer
(23) Design Supply Min Limit. 4...82 (39...180) 30 (86) °C (°F) 2: Installer
(24) Design Supply Max Limit 27...90 (81...194) 90 (194) °C (°F) 2: Installer
(25) Warm Weather Shutdown 0...35 (32...95) 22 (72) °C (°F) 2: Installer
(26) Boost Temp. Increment 0...30 (0...54) 0 (0) °C (°F) 2: Installer
(27) Boost Time Delay 1..120 20 Min. 2: Installer
(28) Night Setback Temp. 0...30 (0...54) 10 (18) °C (°F) 2: Installer
(35) DHW Mode
0) Disabled
1) Tank + sensor
2) Tank + thermostat
0 2: Installer
(113) Max Power DHW 50..100 50 % 2: Installer
(114) Min Power DHW 1..30 1 % 2: Installer
(36) DHW Tank Hyst Down 0...20 (0...36) 5 (9) °C (°F) 2: Installer
(37) DHW Tank Hyst Up 0...20 (0...36) 5 (9) °C (°F) 2: Installer
(38) DHW Tank Supply Extra 0...30 (0...54) 15 (27) °C (°F) 2: Installer
(39) DHW Tank Supp Hyst Dn 0...20 (0...36) 5 (9) °C (°F) 3: Factory
(40) DHW Tank Supp Hyst_Up 0...20 (0...36) 5 (9) °C (°F) 3: Factory
(41) DHW Tank Hold Warm 0...10 (0...18) 5 (9) °C (°F) 3: Factory
(42) DHW Priority
On (DHW)
Off (CH)
Time
On 2: Installer
(43) DHW Max Priority Time 1..255 60 Min. 2: Installer
(44) DHW Pump Overrun 0..900 120 Sec. 2: Installer
(45) DHW Tank PID P 0..1255 100 3: Factory
(46) DHW Tank PID I 0..1255 500 3: Factory
(47) DHW Tank PID D 0..1255 0 3: Factory
(48) DHW/Tank Setpoint 40...71 (104...160) 50 (122) °C (°F) 1: User
(115) DHW Store Setpoint 40...71 (104...160) 57 (135) °C (°F) 1: User
(49) DHW Hysteresis Down 0...20 (0...36) 4 (7) °C (°F) 3: Factory