SSB 6720892984 (2019/02) US
Service reminder | 53
Menu item Sub item / Parameter Range Default Value Units User Level
(136) Mod. Pump Mode
On/Off
Modulating
Fixed 20..100%
On/Off 2: Installer
(137) Mod. Pump Min Power 0..100 40 % 2: Installer
(138) Appliance Type 50..55 50 2: Installer
(139) Dair active Yes, No No 2: Installer
(140) Minimal Flow 0,0..100 50 l/min 2: Installer
(107) Antilegionella Day Sun..Sat Sun Day 2: Installer
(108) Antilegionella Hour 0..23 0 Hour 2: Installer
(183) Hight Limit Test Simulated / Physical Simulated 3: Factory
Module
Cascade
Settings
(72) Permit EmergencyMode Yes/No Yes 1: User
(74) Emergency Setpoint 20...90 (68...194) 70 (158) °C (°F) 2: Installer
(75) Delay Per Start Next Dep 5..255 200 Sec. 2: Installer
(76) Delay Per Stop Next Dep 5..255 180 Sec. 2: Installer
(142) Delay Quick Start Next 5..255 50 Sec. 2: Installer
(143) Delay Per Quick Stop Next 5..255 30 Sec. 2: Installer
(77) Hyst Down Start Module 0...40 (0...72) 5 (9) °C (°F) 2: Installer
(78) Hyst Up Stop Module 0...40 (0...72) 4 (7) °C (°F) 2: Installer
(144) Hyst Down Quick Start 0...40 (0...72) 10 (18) °C (°F) 2: Installer
(145) Hyst Up Quick Stop 0...40 (0...72) 6 (11) °C (°F) 2: Installer
(146) Hyst Up Stop All 0...40 (0...72) 8 (14) °C (°F) 2: Installer
(147) Number of Units 1..8 8 2: Installer
(148) Power Mode
0) Disabled
1) Min burners
2) Max burners
3) Balanced burners
2 2: Installer
(79) Max. Setp. Offset Down 0...40 (0...72) 20 (36) °C (°F) 2: Installer
(80) Max Setp Offset Up 0...40 (0...72) 20 (36) °C (°F) 2: Installer
(81) Start Mod Delay Fact 0..60 60 Min. 2: Installer
(82) Next Module Start Rate 10..100 80 % 2: Installer
(83) Next Module Stop Rate 10..100 25 % 2: Installer
(84) Module Rotation Interval 0..30 5 Days 2: Installer
(149) First Module to Start 1..16 - 2: Installer
(86) PID P 0..1275 50 3: Factory
(87) PID I 0..1275 500 3: Factory
(150) PID Slew Rate Up 0..25,5 1 3: Factory
(151) Casc PID Slew Rate Dn 0..25,5 1 3: Factory
(152) PwrMode2 Min Power 0..100 20 % 2: Installer
(153) PwrMode2 Hysteresis 0..100 40 % 2: Installer
(154) Post-Pump period 0..255 30 Sec. 2: Installer
(155) Frost Protection 10...30 (50...86) 15 (59) °C (°F) 2: Installer
Boiler
Cascade
Settings
(73) Boiler Address
Stand-alone
Managing (1)
Dependent (2..8)
Managing 2: Installer
(156) Permit EmergencyMode Yes/No Yes 1: User
(157) Emergency Setpoint 20...90 (68...194) 70 (158) °C (°F) 2: Installer
(158) Delay Per Start Next Blr. 0..1275 1275 Sec. 2: Installer
(159) Delay Per Stop Next Blr. 0..1275 1275 Sec. 2: Installer
(160) Delay Quick Start Next 0..1275 400 Sec. 2: Installer
(161) Delay Quick Stop Next 0..1275 240 Sec. 2: Installer
(162) Hyst Down Start Boiler 0...40 (0...72) 5 (9) °C (°F) 2: Installer