Service reminder | 79
M.3.3 Boiler Error Log
The Error Log items can be read in blocks of 8 holding registers from error log index 0 to 47 (total 48 error log items).
NOTE: The error log items are not ordered based on the last occurrence when more than 47 errors are stored!
HR #
Access
Description Range
R W
Last Error Index
34000
-
34007
Reserved…
Error Log Index 0
34008 X Error Number See error list.
34009 X Boiler ID: 0=Stand-Alone, 1=Managing, 2-4=Dependent. 0…4
34010 X Timestamp: Day Of Week 0…6 = Sunday…Saturday
34011 X Timestamp: Day Of Month 1…31d
34012 X Timestamp: Month 1…12m
34013 X Timestamp: Year 2000…2255y
34014 X Timestamp: Hour 0...23 (24h notation)
34015 X Timestamp: Minute 0...59min
Error Log Index 1-46
34016
-
34383
X Error Number 2-46
Error Log Index 47
34384 X Error Number See error list.
34385 X Boiler ID: 0=Stand-Alone, 1=Managing, 2-4=Dependent. 0…4
34386 X Timestamp: Day Of Week 0…6 = Sunday…Saturday
34387 X Timestamp: Day Of Month 1…31d
34388 X Timestamp: Month 1…12m
34389 X Timestamp: Year 2000…2255y
34390 X Timestamp: Hour 0...23 (24h notation)
34391 X Timestamp: Minute 0...59min
M.3.4 Boiler Service Reminder
The Service Reminder status and settings can be read/written using the following holding registers.
To check if the Service Reminder is active, the
Hours_Till_Service
holding register should be read.
When the
Hours_Till_Service
value is 0 the service reminder is active.
HR #
Access
Description Range
R W
Service Reminder Counters
33000 X Burn Hours since last service 0…65534 hours.
33001 X Burn Hours till service is required 0…Service_Interval
Service Overdue Counters (history)
33005 X Overdue counter 0 0…65534 hours.
33006 X Overdue counter 1 0…65534 hours.
33007 X Overdue counter 2 0…65534 hours.
33008
-
33018
X Overdue counter 3-13 0…65534 hours.