Electrical connection
49
Greenstar – 6721822579 (2021/01)
7.4 Connecting the LWCO device
NOTICE
System damage or malfunction!
Ensure the air box remains air-tight when routing the LWCO cable to
the outside.
Do not route the LWCO cable through the ignition cable grommet as
appliance malfunction may occur.
Push the existing cable grommet of the fan cable down through air
box sheet.
Slip new cable grommet over the cable.
Insert new cable grommet into the air box sheet.
Push old cable grommet back up and into new cable grommet.
Insert cable of the LWCO device into the second hole of the cable
grommet.
Fig. 60 Mounting the cable grommet (included in scope of delivery)
Install a 24 VAC 20 VA transformer near the boiler.
Follow LWCO manufacturer’s instructions.
Connect the lead labeled BOILER GROUND (green) to pin 2 (center)
of the white plug in the junction box of the wall-mounted gas
condensing boiler.
Connect the two leads labeled 24 V HOT (red) and 24 V COMMON
(white) to the external 24 VAC transformer.
Connect the leads labeled SWITCH CONTACT (yellow) to the TB1
temperature switch ( Fig. 49, page 45) on the Heatronic.
Fig. 61 Wires of a LWCO device with LWCO adapter
[1] LWCO device (Hydrolevel Safgard 1100)
[2] BOILER GROUND (green)
[3] SWITCH CONTACT (yellow)
[4] SWITCH CONTACT (yellow)
[5] 24 V HOT (red)
[6] 24 V COMMON (white)
5.
2.
3.
1.
4.
0010032731-001
2
3
4
5
6
1
6 720 641 933-67.1O