36 | Installation
Copyright (optional information)6 720 643 068 (2011/06)
Gravity heating systems
B Connect the appliance to the existing piping system via
a low-loss header with a sludge separator.
Galvanized radiators or pipes.
To prevent gas formation:
B Do not use galvanized radiators or pipes.
Use of a room temperature control
B Do not install thermostatic valves on radiators in the
primary room.
Anti-freeze
The following anti-freeze fluids are approved:
Nalco (Varidos) FSK
Alphi 11
Glythermin NF
Antifrogen N
Intercool NFP-50 AA
Tyfocor L
NoBurst AL
The following concentrations are approved:
Corrosion inhibitors
The following anti-corrosion agents are approved:
Boiler sealer
This boiler is not approved for use with boiler sealer.
LPG
To protect the appliance against high pressure (ANSI/
Z223.1/NFPA54 (National fuel gas code) or CAN/CSA B
149.1 (Natural Gas and Propane installation code)):
B Install a pressure regulator with a safety valve.
5.1.2 Other important information
The installation of this boiler must comply with all
national and local code and regulations.
Only operate this boiler with the combined air/flue
system specifically designed and approved for it.
Only use approved venting systems per the
manufacturer's instructions.
Do not dispose of untreated boiler condensate in septic
systems.
Inspect the sewer pipes for suitability before disposing
of untreated boiler condensate into them.
Verify with the local authority that disposing of
untreated boiler condensate into public sewer systems
is permitted.
NOTICE: Insufficient antifreeze can
accelerate corrosion.
B Follow manufacturer's instructions on
antifreeze concentration.
B Frost protection level has to be checked
annually during the regular scheduled
maintenance of the condensing boiler.
NOTICE: System damage!
B It is the installer's responsibility to ensure
that the heating system is compatible with
the boiler type and size installed.
B pH-value of the heating water to be kept in
the given ranges (Æ Tab. 13, page 35).
Designation Concentration
Nalco (Varidos) FSK 22 - 55 %
Glythermin NF 20 - 62 %
Intercool NFP-50 AA
0 - 39 %
Tyfocor L
25 - 80 %
NoBurst AL
0 - 55 %
Tab. 15 Anti-freeze
Designation Concentration
Nalco 77381 1 - 2 %
Sentinel X 100 1.1 %
Copal 1 %
Tab. 16 Corrosion inhibitors