EasyManua.ls Logo

Boss MX1-3E - Page 17

Boss MX1-3E
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
17
The table below gives details of all menu items, in the order that they will appear:
#
Menu Item
Function
Default
Value
1
COLD FILL
The required fill pressure, i.e. pump ‘cut-out’ pressure.
The recommended setting is 0.3 BAR above the static pressure
of the system (0.1 Bar per meter of static height).
For example, a 14m high installation will have a static pressure
of 1.4 Bar, making the recommended cold fill pressure 1.7 Bar.
It is not possible to enter a value higher than the current [HIGH
SET] or lower than the current [LOW SET] values.
1.0 Bar
2
HIGH SET
The high pressure alarm setting.
If the pressure in the system reaches this value, the <HIGH
PRESSURE> alarm and common alarm will be activated.
The recommended setting is 10% below the safety valve rating.
For example, if the safety valve rating is 3 Bar, the
recommended setting is 2.7 Bar.
It is not possible to enter a value lower than the current [COLD
FILL] value.
2.7 Bar
3
LOW SET
The low pressure alarm setting.
If the pressure in the system falls below this value, the <LOW
PRESSURE> alarm and common alarm will be activated, and the
pressurisation pumps will not run.
The recommended setting is 0.5 Bar below the [COLD FILL]
pressure.
It is not possible to enter a value higher than the current [COLD
FILL] value.
0.5 Bar
4
DIFFERENTIAL
The differential between the ‘cut-in’ and ‘cut-out’ pressures of
the pressurisation pumps.
The cut-in pressure will be equal to the [COLD FILL] pressure,
minus the differential pressure.
For example, if the [COLD FILL] pressure is set to 1.5 bar, and
the differential set to 0.2 Bar, the pump ‘cut-in’ pressure will be
1.3 Bar (1.5 0.2 = 1.3)
0.2 Bar
5
FLOOD LIMIT
The maximum continuous run time for each of the
pressurisation pumps.
If a pump runs continuously for longer than this period, the
pump will stop and a <FLOOD LIMIT> alarm will be activated.
This is to prevent the unit from pumping large amounts of
water in the event of a large leak/burst pipe.
For very large systems, this may need to be increased.
The value can be changed in increments of 10 minutes, to a
maximum of 990.
10 MINS
6
PUMP 1 COUNT
The cumulative number of pump starts for pump 1.
This is a cumulative counter, the value of which cannot be
modified. If using the engineer’s code, the counter can be reset
to zero by holding the (MUTE) button.
-
7
PUMP 1 HOURS
The cumulative run time in hours for pump 1.
This is a cumulative timer, the value of which cannot be
modified. If using the engineer’s code, the counter can be reset
to zero by holding the (MUTE) button.
-

Related product manuals