54
ENGLISHAPPENDIX A ITALIANO
Table 3: C10 parameter - Fan speed “ “ button limitation.
VALUE DESCRIPTION
0
1 2 3 AUTO
1
1 2 AUTO
2
1 AUTO
3
OFF 1 2 3 AUTO
4
OFF 1 2 AUTO
5
OFF 1 AUTO
6
OFF 1
7
OFF
8
1
9
2
10
3
11
AUTO
12
1 2 3
13
1 2
14
OFF 1 2 3
15
OFF 1 2
Table 4: PARAMETERS C17, C18, C19 - Function associated to 3, 4
and 16 inputs.
VALUE DESCRIPTION
0
No function associated.
1
“Centralised Summer/Winter“ function (closed contact =
summer); P02 parameter congured to 2.
2
“Reversed centralised Summer/Winter“ function (closed
contact = winter); P02 parameter congured to 2.
3
“Economy“ function (closed contact = reduction).
4
“Economy“ function (closed contact = reduction) - display
shows the “
“ (present) or “ “ (absent) icon.
5
“Reversed economy“ function (contact open = reduction).
6
“Reversed economy“ function (contact open = reduction)
- display shows the “
“ (present) or “ “ (absent) icon.
7
“Stop adjustment“ function (closed contact = stop adjustment).
8
“Stop adjustment“ function (closed contact = stop
adjustment) - display shows the
“ (present) or “
(absent) icon.
9
“Stop adjustment“ function (closed contact = stop
adjustment) - display shows the
icon.
10
“Stop adjustment“ function (closed contact = stop
adjustment) - display shows the
icon.
11
Reversed “Stop adjustment“ function (open contact = stop
adjustment).