MF2 CONTROL BOX
CONTROL BOX FOR FORCED DRAUGHT
BURNERS FOR GAS AND OIL FUEL
DESCRIPTION
The MF2 control box is suitable for draught burners for gas
and oil fuel, for civil and industrial applications, with two
flame levels. This control can alternatively employ as
detection flame sensor both a probe, which makes use of
the rectification property of the flame (ionization), and a UV
phototube.
According to TÜV Bayern, Monaco, the control is in
compliance with the German regulation DIN 4788, part 3 ,
for power up to 350KW. It also obtained the DIN-DVGW
89.09fBN approval, now expired and not renewable.
The “Laboratorio di Macchine e Termotecnica del Centro
Studi ed Esperienze” in Rome - Capannelle tested the MF2
control for power up to 2332KW, which obtained the
certification n° 3704/187/77/21 and the approval of the
Ministry of the Interior for fire prevention (circulars n°68 and
n°42).
TECHNICAL DATA:
Supply voltage: 220V (-15%+10%)
50Hz (±5%)
on request: 110V
Operating temperature range: -10°C +60°C
Protection degree: IP40
Starting power consumption: 9 VA
Operating power consumption: 3,5 VA
Contact rating I max
- burner motor: 4 A
- valves (EV1, EV2): 2 A
- ignition transformer: 2 A
- alarm: 1 A
- regulators (T, PA, PG): 6 A
Times:
- prepurge time (TV): 30 s
- safety time (TS): 3 s
- drop out time on running flame failure: <1 s
- delay between EV1 - EV2: 30 s
- postpurge time: 5 s
Flame control
- minimum ionization current: 0,5 µA
- recommended ionization current: 7 µA
- minimum insulation resistance of cable and
flame detector device to earth: > 50 M
- voltage on the detection probe: 350 V
- recommended operating voltage with phototube: >15µ A
Weight including socket: 600 g
CONSTRUCTION
The components of the control are fixed on a frame made
of pressed thermohardening material, with high dielectric
resistance. The enclosure protects the control from
mechanical damages, dust and dirt coming from the
outside during the installation.
Flexible unipolar conductors of different sizes connect the
components of the control, except for the flame detection
and prepurge control circuit, which is mounted on a printed
circuit.
4015_r00 1/4
Question and Answer IconNeed help?

Do you have a question about the BRAHMA MF2 and is the answer not in the manual?

Summary

MF2 CONTROL BOX

DESCRIPTION

Core function, application, and compliance details of the control box.

TECHNICAL DATA

Key specifications including supply voltage, operating temperature, and power consumption.

CONSTRUCTION

Details on the physical build, enclosure material, and internal wiring.

PRODUCT DIMENSIONS AND ACCESSORIES

OVERALL DIMENSIONS

Main overall dimensions of the control box inclusive of connecting sockets.

ACCESSORIES

Information on inbuilt features and optional sensors like phototubes and flame detectors.

CONNECTION SYSTEM

CONNECTION

Details on interconnection system, socket types, and terminal differences.

INSTALLATION AND OPERATION GUIDELINES

DIRECTIONS FOR THE INSTALLATION

Safety precautions and guidelines for correct installation and wiring.

TIMERS

Explanation of timer functions, safety times, and prepurge/postpurge durations.

OPERATING CYCLE

Detailed explanation of the burner control's step-by-step operating sequence.

CONTROL AND SCHEMATICS

RESET OF THE CONTROL

Procedure for resetting the control after a lockout condition.

ELECTRICAL SCHEME

Detailed electrical wiring diagram and component identification.

OPERATING DIAGRAMS AND ABNORMALITIES

CONNECTION DIAGRAM

Visual representation of the wiring connections for the control box.

OPERATING CYCLES

Graphical representation of normal operating sequences.

ABNORMAL OPERATION

Description of fault conditions like air pressure switch issues and responses.

Parasitic flame signal

Details on handling parasitic flame signals and resulting lockouts.