11.2.4.19 Diagnostic value '19.OPEN - Upper endstop'
Requirement:
Display range:
Purpose:
Monitoring the upper endstop 'G.\\OPEN' parameter is activated.
'39.YCLS' Tight closing/fast closing with manipulated variable
(Page 151) parameter is set to one of the following values: 'uP',
'uP do', 'Fu', 'Fu Fd', 'uP Fd', 'Fu do'
0.0 ... 100.0
An indication of the current shift of the upper endstop compared
to its initialization value.
11.2.4.20 Diagnostic value '20.PAVG - Average value of position'
Indication on the display: • OFF
• IdLE
• rEF
• COMP
Purpose: This value shows the last calculated comparison average. Meaning
of the displays:
• OFF: The underlying function is deactivated in the conguration
menu.
• IdLE : Inactive. The function has not been started yet.
• rEF: The reference average is calculated. The function was star‐
ted, and the reference interval is in progress at the moment.
• COMP: The comparison average is calculated. The function was
started, and the comparison interval is in progress at the mo‐
ment.
11.2.4.21 Diagnostic value '21.P0 - Potentiometer value of lower endstop (0%)' / '22.P100 -
Potentiometer value of upper endstop (100%)'
Display range: • NO
• 0.0 ... 100.0
'NO': Changing the low or upper endstop is not possible in the cur‐
rent state of the control valve. Initialize the positioner again.
Condition 1 -
read values
The positioner is initialized.
Purpose 1 Read values
You can use the P0 and P100 parameters to read the values for the
lower endstop (0%) and the upper endstop (100%) of the position
measurement as determined during the automatic initialization. The
values of manually approached end positions are applicable for man‐
ual initialization.