Condition 2 -
change values
• The positioner is initialized and in manual mode (MAN) or auto‐
matic mode (AUT).
• The current position of the actuator is within the range -10% to
+10% of the lower endstop (P0).
• The current position of the actuator is within the range 90% to
110% of the upper endstop (P100).
Purpose 2:
Change values
You can use these two parameters to change the lower endstop (P0)
and the upper endstop (P100).
Since initialization is not usually carried out under process condi‐
tions, the values for the lower endstop (P0) and the upper endstop
(P100) can change when the process is started. These changes can
result from temperature changes with the associated thermal expan‐
sion of the material. If the Monitoring of lower endstop 'F.\\ZERO'
(Page 177) and Monitoring the upper endstop 'G.\\OPEN' (Page 178)
parameters are active, the thresholds set in these two parameters can
be exceeded as a result of thermal expansion. An error message is
output in the display.
The process-dependent thermal expansion might represent the nor‐
mal state in your application. You do not wish to receive an error
message as a result of this thermal expansion. Therefore reset the 'P0'
and/or 'P100' parameters after the process-dependent thermal ex‐
pansion has had its complete eect on the control valve. The proce‐
dure is described in the following.
Description: Procedure for manual mode (MAN)
1. Move the actuator to the desired position of the lower endstop
(upper endstop) using the
and buttons.
2. Switch to diagnostics mode.
3. Go to diagnostic value 21.P0 (22.P100).
4. Apply the setting by pressing the button for at least 5 seconds.
After 5 seconds, '0.0' (with 22.P100: '100.0') is displayed. Result:
The lower endstop (upper endstop) now corresponds to the cur‐
rent position of the actuator.
5. Switch to manual mode (MAN). Result: Values for the upper end‐
stop (lower endstop) have changed.
Procedure for automatic mode (AUT)
1. Check in the display whether the current position of the actuator
is at the desired position of the lower endstop (upper endstop).
2. Switch to diagnostics mode.
3. Go to diagnostic value 21.P0 (22.P100).
4. Apply the setting by pressing the
button for at least 5 seconds.
After 5 seconds, '0.0' (with 22.P100: '100.0') is displayed. Result:
The lower endstop (upper endstop) now corresponds to the cur‐
rent position of the actuator.
5. Switch to automatic mode (AUT).
Diagnostics and troubleshooting
11.2 Diagnostics
SIPART PS2 with 4 to 20 mA/HART
226 Operating Instructions, 10/2020, A5E00074631-AF