281 Issue 1 - Service Manual - BX3
18
5.2 One Flash - Over Heat Condition
Reason Overheat condition
This errors will appear whilst an over temperature is current. The overheat switch or flame
rollout circuit is open and measuring a temperature greater than the temperature of the
switch (See chart below).
The heater’s fan will be forced to operate at its predetermined speed for a specific time period.
Supply air over heat and Flame Roll - out
All Brivis BX3 models have a supply air over heat switch located near the supply air discharge
and is activated when the supply air reaches 90°C on the BX326 but on the BX315 and BX320
are activated at 110°C. Also if the flame roll out occurs the switch will interrupt the 24 Volt power
to the gas valve if flame rollout and over heat occurs.
The following will occur.
The power supply to the gas valve will be terminated.
The fan will operate immediately, if not already operating.
Once the over temperature condition of the switches has cleared and the switch resets (i.e.
switch closes within a specific time), a cool down period will operate for a duration of 120sec.
Then the normal heating cycle can commence again, provided the wall control is still calling for
heat.
Service Check List:
Check the temperature rise value of the supply air thermistor and nearest outlet
temperature, over the room temperature (Return air intake temperature). A 47
0
C.
Temperature rise will indicate a true overheat condition.
Check there are sufficient outlets open on the duct system.
Check the return air filter (if fitted) is sized correctly and is clean.
Check that the fan speed is sufficient for the system so that overheating will not result.
Check the fan motor is functioning correctly, and is not blocked or obstructed.
Check the ducting has not been crushed, damaged or incorrectly sized.
Check the return air intake is not subjected to a high temperature from an external source.
Check the wire loom and plug connections to the switch are not open circuit, i.e. wire
fallen off switch.
Supply air and Flame roll our switch ratings
Unit S/Air over heat switch Flame Roll out switch
BX315 110°C 90°C
BX320 110°C 90°C
BX326 90°C 90°C