Trickle and Boost switch
This is a simple high/low switch with no determined time delay. When the switch is flicked
to boost the system goes into its boost state, the switch then must be put back to trickle
by the occupier for standard operation. (Please note that the aircycle 4.1 system has an
adjustable boost overrun time of up to 15mins).
If using a momentary Switch to put the units into a timed boost using the overrun; you
Must press the momentary switch for at least 4 seconds, or the unit will enter purge
mode.
*The items detailed above are examples of the types of Manual Control Options that are
typically used in conjunction with the Brookvent aircycle 4.1 *
9.0 Trouble Shooting
The MVHR unit is not running?
1. Check that the unit is connected to a 3amp fused spur as per the wiring
instructions.
2. Check that there is a live feed to the fused spur. This should only be completed
by a qualified electrician.
3. Check that the 3-amp fuse has not tripped/blown. This should only be completed
by a qualified electrician.
4. Check that all the spindles are in the full power position (fans can take a few
seconds to start up).
The system is constantly in Boost mode?
New houses can be quite damp with items drying out; this can cause the inbuilt
humidistat to activate. Turning the internal humidistat up to 100% RH will allow the unit
to switch back to trickle speed (This may take 15min depending on the boost over-run
setting which can be adjusted to 0min on the control panel to temporarily disable).
Remember to turn the humidity stat back to its factory set of 70% RH upon achieving
the commissioned and reset the boost over-run time, if required).