DETAILED COOLING CAPACITIES# (CONTINUED)
{ Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
} Sensible capacities shown are based on 80_F(27_C) entering air at the indoor coil. For sensible capacities at other than 80_F(27_C), deduct 835 Btuh
(245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80_F(27_C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air per degree a bove 80_F(27_C).
# Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per AHRI standard 210/240---2008. If additional tubing length an d/or indoor u n it is l ocated above outdoor unit, a slight variation in capacity
may occur.
** System kw is total of indoor and outdoor unit kilowatts.
EWB — Entering Wet Bulb
NOTE: When the required data fall between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.