EasyManuals Logo

Bryant 574B User Manual

Bryant 574B
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #5 background imageLoading...
Page #5 background image
5
PHYSICAL DATA
Required filter sizes shown are based on the larger of the ARI (Air Conditioning & Refrigeration Institute) rated cooling air-
flow or the heating airflow velocity of 300 ft/min for throwaway type or 450 ft/min for high-capacity type. Air filter pressure
drop for non-standard filters must not exceed 0.08 in. wg.
*
Based on altitude of 0 to 2000 ft.
UNIT SIZE 574B 024040 030040 030060 036060 036090 042060 042090
NOMINAL CAPACITY (ton)
2 2-1/2 2-1/2 3 3 3-1/2 3-1/2
OPERATING WEIGHT (lb)
350 388 388
COMPRESSORS
Scroll
Quantity
1
REFRIGERANT (R-410A)
Quantity (lb)
7.3 9.5 9.5
REFRIGERANT METERING DEVICE
Indoor
TXV
CONDENSER COIL
RowsFins/in.
Face Area (sq ft)
2/21
11.95
2/21
13.7
2/21
13.7
CONDENSER FAN
Nominal Cfm
Diameter (in.)
Motor Hp (Rpm)
2350
22
1/8 (825)
2350
22
1/8 (825)
2350
22
1/8 (825)
EVAPORATOR COIL
Rows—fins/in.
Face Area (sq ft)
3/15
3.7
4/15
3.7
4/15
3.7
EVAPORATOR BLOWER
Nominal Airow (Cfm)
Size (in.)
Motor Hp (Rpm)
800
10 x 10
1/2
1150
11 x 10
3/4
1150
11 x 10
3/4
FURNACE SECTION*
Burner Orice No. (QtyDrill Size)
Natural
Burner Orice No. (QtyDrill Size)
Propane
244
250
238
246
338
346
HIGH-PRESSURE SWITCH (psig)
Cutout
Reset (Auto.)
610 ± 15
420 ± 25
LOSS-OF-CHARGE/LOW-PRESSURE SWITCH
(Liquid Line) (psig)
Cutout
Reset (Auto.)
20 ± 5
45 ± 10
RETURN-AIR FILTERS (in.)
Throwaway
20 x 24 x 1 20 x 24 x 1 20 x 24 x 1 20 x 24 x 1 20 x 24 x 1 24 x 30 x 1 24 x 30 x 1