35
Table 13 -- Dry Coil Air Delivery -- Horizontal and Downflow Discharge -- 208/230 VAC Single Phase Models (Cont)
Unit
Heating Rise
Range
Motor
Speed
Wire
Color
Allowable Functions
External Static Pressure (in. WC)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
30040
25 --- 55
o
F
Low Stage,
25 --- 55
o
F
High Stage
Low
3
Blue
Low Stage Gas Heating
Alternate Low Stage
Cooling
CFM 714 525 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
BHP 0.08 0.07 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
Low Stage
Heat Rise
o
F
(
o
C)
27
(15)
37
(21)
NA NA NA NA NA NA NA NA
High Stage
Heat Rise
o
F
(
o
C)
NA NA NA NA NA NA NA NA NA NA
Med---Low
1
Pink
Low Stage Cooling
Alternate Low Stage
Gas Heating
Alternate High Stage
Gas Heating
CFM 831 765 670 586 466 299 --- --- --- --- --- --- --- ---
BHP 0.11 0.12 0.12 0.13 0.13 0.14 --- --- --- --- --- --- --- ---
Low Stage
Heat Rise
o
F
(
o
C)
NA
26
(14)
29
(16)
33
(19)
42
(23)
NA NA NA NA NA
High Stage
Heat Rise
o
F
(
o
C)
36
(20)
39
(22)
45
(25)
51
(28)
NA NA NA NA NA NA
Medium
4
Red
High Stage Gas Heating
Alternate Low Stage
Cooling
Alternate Low Stage
Gas Heating
CFM 831 765 670 586 466 299 --- --- --- --- --- --- --- ---
BHP 0.11 0.12 0.12 0.13 0.13 0.14 --- --- --- --- --- --- --- ---
Low Stage
Heat Rise
o
F
(
o
C)
NA
26
(14)
29
(16)
33
(19)
42
(23)
NA NA NA NA NA
High Stage
Heat Rise
o
F
(
o
C)
36
(20)
39
(22)
45
(25)
51
(28)
NA NA NA NA NA NA
M e d --- H i g h
2
Orange
High Stage Cooling
Alternate High Stage
Gas Heating
CFM 1139 1069 1012 937 870 786 724 626 512 381
BHP 0.22 0.23 0.24 0.24 0.25 0.26 0.26 0.27 0.27 0.28
Low Stage
Heat Rise
o
F
(
o
C)
NA NA NA NA NA NA NA NA NA NA
High Stage
Heat Rise
o
F
(
o
C)
26
(15)
28
(16)
30
(16)
32
(18)
34
(19)
38
(21)
41
(23)
48
(27)
NA NA
High Black
High Static, High Stage
Cooling Only
CFM 1531 1460 1382 1301 1209 1114 1003 890 764 629
BHP 0.53 0.52 0.50 0.48 0.46 0.44 0.42 0.40 0.37 0.35
Notes:
*Air delivery values are without air filter and are for dry coil (See Wet Coil Pressure Drop Table)
“High Static, High Stage Cooling” --- Only to be used for high stage cooling function (Not allowed for any gas heating function)
1
F actory-shipped low stage cooling speed
2
Factory-shipped high stage cooling speed
3
Factory-shipped low stage gas heating speed
4
Factory-shipped high stage gas heating speed
Shaded areas indicate speed/static combinations that are not permitted for dehumidification speed.
”NA” = Not allowed for particular gas heating speed
577E