ARI* CAPACITY RATINGS — 581B036-150
LEGEND
*Air-Conditioning & Refrigeration Institute.
†Applies only to units with capacity of 65,000 Btuh or less.
**The IPLV is not applicable to single-compressor units.
NOTES:
1. Rated in accordance with ARI Standard 210/240 (036-120 units) or
360 (150 units) and 270 (036-150 units).
2. Ratings are net values, reflecting the effects of circulating fan heat.
Ratings are based on:
Cooling Standard: 80 F db, 67 wb indoor entering-air temperature
and 95 F db outdoor entering-air temperature.
IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature
and 80 F db outdoor entering-air temperature.
3. All 581C024-060 and 581B036-150 units are in compliance with
ASHRAE 90.1-1999 Energy Standard for minimum SEER and EER
requirements. Refer to state and local codes or visit the following
website: http://bcap-energy.org
to determine if compliance with this
standard pertains to a given geographical area of the United States.
4. All 581C024-060 and 581B036-120 units are Energy Star certified.
HEATING CAPACITIES AND EFFICIENCIES — 581B036-150
208/230-1-60 — SINGLE-STAGE GAS HEAT
LEGEND
AFUE — Annual Fuel Utilization Efficiency.
208/230-1-60 — SINGLE-STAGE GAS HEAT — LOW NOx
LEGEND
AFUE — Annual Fuel Utilization Efficiency.
UNIT
581B
NOMINAL
TONS
COOLING
(Btuh)
TOTAL
kW
SEER† EER
SOUND RATING
dB
IPLV
036 3 36,000 3.21 13.0 11.20 76 **
048 4 46,000 4.25 13.0 11.05 76 **
060 5 61,000 5.55 13.0 11.00 80 **
072 6 73,000 6.70 11.00 80 **
090 7
1
/
2
90,000 8.18 11.00 82 11.6
102 8
1
/
2
103,000 8.90 11.60 82 12.8
120 10 120,000 10.91 11.00 84 11.4
150 12
1
/
2
138,000 14.40 9.6 86 10.3
EER Energy Efficiency Ratio
IPLV Integrated Part-Load Value
SEER Seasonal Energy Efficiency Ratio
Sizes 036-120
Only
Sizes 150
Only
UNIT
581B
INPUT CAPACITY OUTPUT CAPACITY
TEMPERATURE
RISE (°F)
MINIMUM HEATING
AIRFLOW (CFM)
EFFICIENCY
AFUE (%) Steady State (%)
036072 72,000 58,000 25-55 1004 82.8 82.0
036115 115,000 90,000 55-85 1002 80.0 80.0
048072 72,000 58,000 25-55 1004 82.8 82.0
048115 115,000 90,000 35-65 1320 81.0 81.0
048150 150,000 118,000 50-80 1396 80.4 80.0
060072 72,000 58,000 25-55 1004 82.8 82.0
060115 115,000 92,000 35-65 1327 81.0 81.0
060150 150,000 118,000 50-80 1314 80.4 80.0
UNIT
581B
INPUT CAPACITY OUTPUT CAPACITY
TEMPERATURE
RISE (°F)
MINIMUM HEATING
AIRFLOW (CFM)
EFFICIENCY
AFUE (%) Steady State (%)
036060N 60,000 50,000 20-50 930 80.2 81.2
036090N 90,000 74,000 30-60 1150 81.0 81.4
048060N 60,000 50,000 20-50 930 80.2 81.2
048090N 90,000 74,000 30-60 1150 81.0 81.4
048120N 120,000 101,000 40-70 1340 80.7 82.4
060060N 60,000 50,000 20-50 930 80.2 81.2
060090N 90,000 74,000 30-60 1150 81.0 81.4
060120N 120,000 101,000 40-70 1340 80.7 82.4