EasyManua.ls Logo

Bryant 582A Series - Page 2

Bryant 582A Series
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
REQ’D CLEARANCES FOR OPERATION AND SERVICING. in. (mm)
Evaporator coil access side ......................36(914)
Power entry side (except for NEC requirements) ..............36(914)
Unit top .............................48(1219)
Side opposite ducts .........................36(914)
Duct panel ...........................12(304.8)*
*Minimum distances: If unit is placed less than 12 in. (304.8 mm) from wall system, then the
system performance may be compromised.
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)
Top of unit ............................14(355.6)
Duct side of unit ...........................2(50.8)
Side opposite ducts ........................14(355.6)
Bottom of unit ..........................0.50 (12.7)
Flue panel ............................36(914.4)
NEC REQ’D CLEARANCES. in. (mm)
Between units, power entry side ...................42(1066.8)
Unit and ungrounded surfaces, power entry side ..............36(914)
Unit and block or concrete walls and other grounded
surfaces, control box side .....................42(1066.8)
UNIT
582A
ELECTRICAL
CHARACTERISTICS
UNIT WEIGHT UNIT HEIGHT in. [mm] CENTER OF GRAVITY in. [mm]
lb kg A X Y Z
582A018040 208/230-1-60 249.0 113.2 35.02 [889.5] 20.0 [508.0] 14.0 [355.6] 15.0 [381.0]
582A024040/060 208/230-1-60 280.0 127.3 35.02 [889.5] 22.5 [571.5] 13.0 [330.2] 15.0 [381.0]
582A030040/060 208/230-1-60, 208/230-3-60 280.0 127.3 35.02 [889.5] 21.5 [546.1] 13.75 [349.3] 15.0 [381.0]
582A036060/090 208/230-1-60, 208/230-3-60, 460-3-60 314.0 142.7 35.02 [889.5] 22.5 [571.5] 14.0 [355.6] 13.0 [330.2]
582A042060/090 208/230-1-60, 208/230-3-60, 460-3-60 355.0 161.4 35.02 [889.5] 21.5 [546.1] 13.5 [342.9] 13.0 [330.2]
UNIT
ELECTRICAL
CHARACTERISTICS
UNIT WEIGHT UNIT HEIGHT in. [mm] CENTER OF GRAVITY in. [mm]
lb kg A X Y Z
583A024040/060 208/230-1-60 290.0 639.3 35.02 [889.5] 22.0 [558.8] 14.5 [368.3] 16.0 [406.4]
583A030040/060 208/230-1-60, 208/230-3-60 313.0 690.0 39.02 [991.1] 22.0 [558.8] 15.3 [387.4] 17.6 [447.0]
583A036060/090 208/230-1-60, 208/230-3-60, 460-3-60 321.0 707.7 35.02 [889.5] 22.0 [558.8] 15.3 [387.4] 16.5 [419.1]
LEGEND
CG Center of Gravity
COND Condenser
EVAP Evaporator
NEC National Electrical Code
REQ’D Required
NOTE: Dimensions are in mm [in.]
Fig. 2 582A018-042 and 583A024-036 Unit Dimensions
—2—

Related product manuals