11
and thei r fact ory default set t i ngs. Not all numbers are used in the Legacy Seri es because
not al l options are available in this series - and numbering is consi s t ent across the T1,
T2, and T6 thermost at lines .
Configuration Options - Summary:
Option 01 - Equipment type
Option 03* - Fahrenheit/Centigrade
Option 04 - Fan (G) on with W output
Option 07 - Zoning
Option 10 - Reversing valve
Option 11 - Minimum deadband between heating and cooling setpoints
Option 12 - Smart Recovery (programmable models only)
Option 13 - Room air temperature offset adjustment
Option 15 - Auto Changeover availability
Option 16 - Maximum cycles per hour
Option 17 - Time between equipment stages
Option 18* - Continuous backlighting
Option 21* - Keypad lockout
Option 24* - Progr ammable/non-programmabl e (program mabl e models only)
Option 25* - Number of programmable periods per day
Option 26 - Minimum cooling setpoint
Option 27 - Maximum heating setpoint
Option 99 - Reset to factory defaults
Those options marked with an asterisk are also adjustable by the homeowner. See
Owner’s Manual for further information.