3
SPECIFICATIONS
MODEL FE4A
* Modular Unit
+ Nominal airow = outdoor unit size (tons) x 350 cfm. Airow may be modied by system operating mode.
SIZE 002 003 005 006*
SHIPPING WEIGHT (Lb) 135 150 172 207
REFRIGERANT Puron (R-410A)
Refr. Metering Device TXV
Size 2 Ton3 Ton4 Ton4 Ton
COIL
Type A Slope A A
Rows - Fins/In. 3 - 14.5
Face Area (sq-ft) 3.46 3.46 5.93 7.42
MATCHES OUTDOOR UNIT SIZES
Nominal Cooling Tons 1.5, 2, 2.5, 3 2, 2.5, 3, 3.5 2.5, 3, 3.5, 4 3, 3.5, 4, 5
FAN
Upow, Downow, HorizontalAir Discharge
CFM/TON (Nominal) 350+
MOTOR HP (ECM) 1/2 1/2 1/2 3/4
FILTER 21-1/2 x 16-3/8 21-1/2 x 18-7/8 21-1/2 x 18-7/8 21-1/2 x 23-5/16