PERFORMANCE DATA Continued
MINIMUM CFM FOR ELECTRIC HEATER APPLICATION
NOTE:
Heater Only—Air conditioner with electric heater application.
These airflows are the minimum acceptable air flows as U.L. listed.
UNIT SIZE
HEAT PUMP
UNIT
SIZE
CFM
Heater Size KW
5 9, 10 15 20 24, 30
002
Heater Only
018
024
030
036
625
650
675
850
1000
650
650
775
950
1050
825
—
900
1050
1125
1025
—
—
1125
1225
—
—
—
—
—
003
Heater Only
024
030
036
042
675
675
850
1025
1150
725
875
950
1075
1200
850
—
1100
1150
1300
1100
—
1150
1275
1400
—
—
—
—
—
005
Heater Only
030
036
042
048
675
850
1025
1150
1325
725
950
1075
1200
1325
850
1100
1150
1300
1400
1100
1150
1275
1400
1500
1400
—
—
—
1600
006
Heater Only
036
042
048
060
1050
1150
1150
1325
1650
1050
1150
1150
1325
1650
1050
1350
1350
1400
1650
1100
1350
1575
1600
1750
1750
—
—
1750
1750