COMMERCIAL IN CONFIDENCE
Page 8
1.8 Level A – parameters in address order (9500 only)
Parameter
Name
Size Address
(hex)
R/W ModBus
Function
read/write
Internal Storage, Step rate in
Internal units, Limits
Comments
An.Hi 2 02D9 RW 3/6 AnHi
Step=1
min=-1999, max=9999
An.Lo 2 02DB RW 3/6 AnLo
Step=1
min=-1999, max=9999
Hi.In 2 02DD RW 3/6 HiIn * 10
step=0.1
min=0.1, max 50.0
HiIn must always be 0.1 above
the LoIn setting
Lo.In 2 02DF RW 3/6 LoIn * 10
step=0.1
min=0.0, max 49.9
DECP 1 03E1 RW 3/6 0=0000, 1=000.0, 2=00.00 Decp over-rides the Disp setting
in level 2 while linear input
selected
SP3.A 1 03E2 RW 3/6 0=none, 1=dvhi, 2=dvlo, 3=band,
4=fshi, 5=fslo
9500P 7=EOP
SP3.B 1 03E3 RW 3/6 0=none, 1=ltch, 2=hold, 3=ltho
Brn.3 1 03E4 RW 3/6 0=upsc, 1=dnsc
Rev.3 1 03E5 RW 3/6 0=3d, 1=3r
Set.3 2 02E8 RW 3/6 Degrees * 10 [LIN]
step=0.1
min=0.0, max=2500
When LIN sensor selected
max=9999
Hys.3 2 02EA RW 3/6 Hys3 * 10 [LIN]
step=0.1
min=0.1, max=100% of HiSc
Note: The level A menu is only available in the 9500 instrument.
1.9 Level P – parameters in address order (9500P only)
Parameter
Name
Size Address
(hex)
R/W ModBus
Function
read/write
Internal Storage, Step rate in
Internal units, Limits
Comments
MaxProg 1 033A R 3 Maximum Program Number Generated by the instrument, do
not write to this location.
Prog 1 036C RW 3/6 Program Number
min=1, max=MaxProg
To start a program write the
number of the program to run
and then set the value of
Sprn(Level 1) to ON or HOLD
Note: the program will not start
until after the exit program mode
Note: The level P menu is only available in the 9500P instrument.
Note: The other elements of the programmer (Level P) menu are unavailable from the communications
interface.