F
AULT DESCRIPTION
A
LERTS
P
OSSIBLE CAUSE OF FAULT
O
PERATIONS TO BE PERFORMED
Domestic hot
water is not
heated
blinking
icon
primary circuit shut-off valves closed open the valves
modulating valve actuator disconnected from valve body reconnect actuator
modulating valve actuator faulty call qualified personnel to have it replaced
DHW temperature probe cable inverted with heating probe restore correct connection
presence of air in the system vent the system
electronic regulator not working call qualified personnel to have it replaced
valve obturator blocked in closed position call qualified personnel to have it replaced
centralised system not working/cold contact person in charge of system
error code 6 active
DHW temperature probe disconnected reconnect probe
DHW temperature probe faulty call qualified personnel to have it replaced
error code 80 active
incorrect wiring/no credit check electrical connections/top up credit
fixed
icon
DHW priority flow meter disconnected reconnect flow meter
DHW priority flow meter faulty call qualified personnel to have it replaced
icon absent
DHW production not enabled
enable DHW production by means of HIU
interface
display is off
electric supply cut off restore HIU electric supply
protection fuse burnt out call qualified personnel to have it replaced
The water is hot
but does not
reach the
desired
temperature
blinking
icon
domestic water cycle temperature set point too low increase set point
primary return temperature limitation intervention
change the return temperature set
point/disable the function
primary circuit strainer of the HIU clogged call qualified personnel to have it serviced
exchanger partly clogged call qualified personnel to have it serviced
modulating valve actuator faulty call qualified personnel to have it replaced
DHW temperature probe cable inverted with heating probe restore correct connection
excessive demand for DHW decrease demand
electronic controller not working call qualified personnel to have it replaced
centralised system temperature insufficient contact person in charge of system
primary circuit flow rate insufficient contact person in charge of system
primary flow rate limit too low contact person in charge of system
Hot water
temperature is
too high
blinking
icon
domestic water cycle temperature set point too high decrease set point
DHW temperature probe cable inverted with heating probe restore correct connection
modulating valve actuator faulty call qualified personnel to have it replaced
valve obturator blocked in intermediate or open position call qualified personnel to have it replaced
electronic regulator not working call qualified personnel to have it replaced
primary circuit excessive flow rate due to DPCV valve
malfunction
call qualified personnel to have it replaced
Antilegionella cycle in progress contact person in charge of system
Hot water flow
rate is
insufficient
blinking
icon
HIU strainer clogged call qualified personnel to have it serviced
possible domestic water system shut-off valves
partially closed
open the valves
insufficient pressure in centralised domestic water circuit call qualified personnel to have it serviced
Hot water flow
rate is zero
-
possible domestic water system shut-off valves closed open the valves
no cold water in centralised domestic circuit call qualified personnel to have it serviced
HIU strainer completely clogged call qualified personnel to have it serviced
exchanger completely blocked call qualified personnel to have it serviced
Troubleshooting

Other manuals for CALEFFI SATK32107 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CALEFFI SATK32107 Series and is the answer not in the manual?

CALEFFI SATK32107 Series Specifications

General IconGeneral
BrandCALEFFI
ModelSATK32107 Series
CategoryRecording Equipment
LanguageEnglish

Related product manuals