Barrier indicator light (contact rated for: 24 V AC - 3 W max).
It warns of the barrier status, see function F 10.
Warning devices
Dome flashing light and/or luminous cord
(Contact rated for: 24 V - 25 W max.)
It flashes during the boom's opening and closing
phases.
Photocells
DIR
Photocells
DELTA-S
Photocells
DELTA
Safety devices
Configure contact CX or CY (NC), input for safety devices
such as photocells, that are EN 12978 regulation compliant.
See CX input functions (Function F2) or CY (Function F3)-
C1 reopening while closing. When the boom is closing,
opening the contact causes its movement to invert until fully
opened;
C4 obstruction wait. Stopping the boom, if it is moving, with
resumption of movement after the obstruction is removed.
C5 immediate closing. Closing the boom after a vehicle has
passed through the operating area of the safety devices.
C9 immediate closing with obstruction wait when closing.
Closing the boom after a vehicle has passed through the
operating area of the safety devices.
During the closing phase, the devices also perform the
function of C4 obstruction wait.
If unused, contacts CX and CY should be deactivated
during programming.