FCP manual
Code +030220391 – rel 1.2 25/03/08
28
PB3E enable probe input B3
type and Carel supervisor address digital var. 8
Modbus address read/write coil 8
resolution and unit of measure 1
range 0/1
default 0
Parameter used to enable probe input B3 and, as a consequence, the outside temperature compensation function. The reading of the probe and any alarms due to
probe faults are only activated if the input is enabled.
PB3E=0 disabled
PB3E=1 enabled
ELIN enable output linearisation
type and Carel supervisor address digital var. 9
Modbus address read/write coil 9
resolution and unit of measure 1
range 0/1
default 1
Parameter used to enable the linearisation of the output voltage, compensating the sinusoidal relationship between phase and voltage.
ELIN=0 disabled
ELIN=1 enabled
ELPL select phase control function
type and Carel supervisor address digital var. 10
Modbus address read/write coil 10
resolution and unit of measure 1
range 0/1
default 0
Parameter used to select the type of phase control.
ELPL=0 short impulse (around 3ms)
ELPL=1 long impulse (from the moment of switching until the end of the mains half period)
The parameter has no meaning if the selection of the type of phase control is associated with dipswitch 4 (par. DIP4).
MOID operating logic of ID1
type and Carel supervisor address digital var. 11
Modbus address read/write coil 11
resolution and unit of measure 1
range 0/1
default 0
Parameter used to select the operating logic of digital input ID1.
MOID=0 normally closed
MOID=1 normally open
EOVR enable Override function
type and Carel supervisor address digital var. 15
Modbus address read/write coil 15
resolution and unit of measure 1
range 0/1
default 0
Variable used to enable the Override function and consequently force the output to the value defined by the OUTV parameter, irrespective of the value calculated by
the control algorithm
PB3E=0 disabled
PB3E=1 enabled
The variable is forced to zero (Override disabled) on power-up and in any case 10 seconds after no more data is received from the serial line.
FDEF reset parameter default values
type and Carel supervisor address digital var. 16
Modbus address read/write coil 16
resolution and unit of measure 1
range 0/1
default 0
Variable used to reset the default values of the parameters.
FDEF=0 no action
FDEF=1 reset default
The value is automatically set back to 0 when the function is activated. It is not saved in the EEPROM.