EasyManuals Logo

Carel IR32 Series User Manual

Carel IR32 Series
82 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #56 background imageLoading...
Page #56 background image
OUT1: deve essere programmata come uscita di allarme atti-
va solo in caso di allarme di “Bassa”. Si deve quindi modifica-
re la dipendenza DIPENDENZA=C34 che passa da 1 a 9 (o
10 se si vuole lavorare con relè normalmente ON). I parame-
tri C35, C36, C37 non hanno più rilevanza e restano invariati.
OUT2: si svincolerà dal funzionamento DIFFERENZIALE
cambiando la DIPENDENZA da 1 a 2: quindi DIPENDEN-
ZA=C38=2. La logica è di tipo Direct e comprende tutto
P2, quindi INSERZIONE=C40 diventa 100, e DIFFEREN-
ZIALE/LOGICA=C41 diventa -100. St2 sarà ovviamente
impostato a 8 e P2 rappresenta la variazione minima
necessaria per riavviare l’unità, una volta che si è arresta-
ta per “Bassa” temperatura, es P2=4.
OUT3 e OUT4: negli strumenti con 4 uscite, il Modo 1
assegna ad ogni uscita una isteresi pari al 25% del differenziale
P1. Nell’esempio considerato le uscite effettivamente utilizzate
per la regolazione sono 2, per cui si vuole che l’isteresi di ogni
uscita sia il 50% di P1. È necessario quindi cambiare i
parametri INSERZIONE e DIFFERENZIALE/ LOGICA delle
uscite indicate in modo che si adattino alla nuova situazione.
In pratica si dovrà porre:
OUT3:
INSERZIONE=C44 passa da 75 a 50
DIFFERENZIALE/LOGICA=C45, passa da -25 a -50.
OUT4:
INSERZIONE=C48 resta a 100
DIFFERENZIALE/LOGICA = C49 passa da -25 a -50.
Il disegno riassume la logica di funzionamento della
regolazione:
Esempio 13
Si vuole pilotare 3 bruciatori di una caldaia per portare
l’acqua alla temperatura St1. È richiesta un’uscita di allar-
me che deve essere attivata nel caso in cui l’acqua superi
un limite di “Alta” temperatura o in caso sia segnalato un
blocco dell’impianto.
Soluzione: supposto che il segnale di blocco sia disponi-
bile come contatto pulito, si potrà utilizzare l’ingresso digi-
tale per la sua gestione. Si dovrà poi configurare un’uscita
come allarme (DIPENDENZA=5 o 6).
Il Modo di partenza può essere lo standard, ovvero C0=2.
OUT1: program it as active alarm output to be used in the
event of low temperature alarm; in this case modify
dependence (DEPENDENCE=C34) from 1 to 9 (or 10 if
you want normally open relays).You do not need to
modify C35, C36, C37.
OUT2: in order to make idle the DIFFERENTIAL function,
change DEPENDENCE from 1 to 2: DEPENDENCE=C38=2.
The controller will perform in the DIRECT logic and will
include the entire value of P2:Therefore old ENERGIZATION=
C40 becomes C40=100, and old DIFFERENTIAL/LOGIC=C41
becomes C41=-100. Set St2=8. P2 indicates the minimum
variation necessary to re-start the unit following a low
temperature condition (e.g. P2=4).
OUT3 and OUT4: when using 4-output controllers, setting
Mode 1 means to give each output a hysteresis corresponding
to 25% of the differential P1. In the example shown below,
there are 2 actual control outputs (OUT3 and OUT4) so
the hysteresis of each output should correspond to 50%
of P1. It is therefore necessary to change ENERGIZATION
and DIFFERENTIAL/LOGIC referrring to the indicated output
so as to meet the new application requirements.
In short:
OUT3:
ENERGIZATION=C44 changes from 75 to 50
DIFFERENTIAL/LOGIC=C45 changes from -25 to -50.
OUT4:
ENERGIZATION=C48 remains 100
DIFFERENTIAL/LOGIC=C49 changes from -25 to -50.
The graph below shows the new control logic:
Example no. 13
Control and regulation of 3 boiler burner units so as to
bring the water temperature to St1.You need one alarm
output that will energise in the event the water temperatu-
re rises above the “High” temperature threshold or in the
event the system locks.
Solution: Use the digital input (voltage-free contact) to
regulate the 'system lock' signal.Then configure another
output as alarm output (DEPENDENCE=5 or 6).
As for the Mode, there is no need to change its standard
setting, that is C0=2.
53
St1=-5
ON
P1=2
OFF
NTC1-NTC2
ON
ON
OUT1
OUT2
OUT3
OUT4
St2=8
NTC1=T2
P25=6
P2
12
Alarm
P27
Fig.40

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carel IR32 Series and is the answer not in the manual?

Carel IR32 Series Specifications

General IconGeneral
BrandCarel
ModelIR32 Series
CategoryController
LanguageEnglish

Related product manuals