ir33 universale +030220801 - rel. 2.1 - 21.06.2011
3.2 Keypad
Pressing the button alone:
If pressed for more than 5 seconds, accesses the menu for setting the type P parameters (frequent);
Mutes the audible alarm (buzzer) and deactivates the alarm relay;
When editing the parameters, pressed for 5 s, permanently saves the new values of the parameters;
When setting the time and the on/o times returns to the complete list of parameters.
Pressing together with other buttons
If pressed for more than 5 seconds together with Set, accesses the menu for setting the type C parameters (con guration);
If pressed for more than 5 seconds together with UP, resets any alarms with manual reset (the message ‘rES’ indicates the alarms
have been reset); any alarm delays are reactivated;
Start up
If pressed for more than 5 seconds at start up, activates the procedure for loading the default parameter values.
(UP) Pressing the button alone:
Increases the value of the set point or any other selected parameter
Pressing together with other buttons
If pressed for more than 5 seconds together with Prg/mute, resets any alarms with manual reset (the message ‘rES’ indicates the
alarms have been reset); any alarm delays are reactivated.
(DOWN) Pressing the button alone:
Decreases the value of the set point or any other selected parameter.
In normal operation accesses the display of the second probe, digital inputs and set point.
Pressing the button alone:
If pressed for more than 1 second displays and/or sets the set point
Pressing together with other buttons
If pressed for more than 5 seconds together with Prg/mute, accesses the menu for setting the type C parameters (con guration).
Tab. 3.b
3.3 Programming
The operating parameters can be modi ed using the front keypad. Access
di ers depending on the type: set point, frequently-used parameters (P)
and con guration parameters (c). Access to the con guration parameters
is protected by a password that prevents unwanted modi cations or
access by unauthorised persons. The password can be used to access and
set all the control parameters.
3.3.1 Setting set point 1 (St1)
To change set point 1 (default =20°C):
press Set: the display shows St1 and then the current value of St1;
press or to reach the desired value;
press Set to con rm the new value of St1;
the display returns to the standard view.
Fig. 3.c
3.3. 2 Setting set point 2 (St2)
In operating modes 6, 7, 8 and 9 (see the chapter on Functions) and when
c19=2,3,4 and 7 (see the chapter on Control) the controller works with
two set points.
To change set point 2 (default =40 °C):
press Set: twice slowly: the display shows St2 and then the current
value of St2;
press or until reaching the required value;
press Set to con rm the new value of St2;
the display returns to the standard view.
Fig. 3.d
3.3.3 Setting type P parameters
Type P parameters (frequents) are indicated by a code beginning with the
letter P, followed by one or two numbers.
1. Hold the button, after 3 seconds the displays shows the
rmware revision code (e.g. r2.1) is shown, after 5 seconds (in the
event of alarms,  rst the buzzer is muted) the code of the  rst type P
modi able parameter, P1;
2. Press or until reaching the desired parameter. When
scrolling, an icon on the display shows the category the parameter
belongs to (see the table below and the table of parameters);
3. Press Set to display the associated value;
4. Increase or decrease the value using or respectively, until
reaching the desired value;
5. Press Set to temporarily save the new value and return to the display
of the parameter code;
6. Repeat operations from 2) to 5) to set other parameters;
7. To permanently save the new values of the parameters, press
for 5 s, thus exiting the parameter setting procedure.
Important:
If no button is pressed for 10s, the display starts  ashing,
and after 1 minute automatically returns to the standard display,
without saving the changes.
To increase the scrolling speed, press and hold the / button
for at least 5 seconds
before accessing type P parameters, the  rmware revision is displayed
for 2 seconds, according to the procedure described at the start of
paragraph 3.3.3
Fig. 3.e