EasyManua.ls Logo

Carel ir33 Universale - Page 42

Carel ir33 Universale
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
42
ENG
ir33 universale +030220801 - rel. 2.1 - 21.06.2011
6.5.6 Enable logic on absolute set point & di erential
set point (parameter c19=5,6)
When c19=5 the value read by probe B2 is used to enable control logic in
both direct and reverse mode.
If c19=6 the value considered is B2-B1.
Par. Description Def Min Max UoM
c19 Operation of probe 2
5=enable logic on set absolute
6=enable logic on set di erential
Validity: c0=1 or 2
00 6-
c66 Enabling threshold in direct mode
Validity: c0=1 or 2
-50
(-58)
-50
(-58)
150
(302)
°C/°F
c67 Enabling threshold in reverse mode
Validity: c0=1 or 2
150
(302)
-50
(-58)
150
(302)
°C/°F
c66 Start enabling interval
Validity: c0=1 or 2
-50
(-58)
-199
(-199)
800
(800)
°C(°F)
c67 End enabling interval
Validity: c0=1 or 2
150
(302)
-199
(-199)
800
(800)
°C(°F)
Tab. 6.g
“Reverse control with enable logic
Looking at the example of a controller with two outputs, one of which
ON/OFF and the other 0 to 10 Vdc. When the temperature read by probe
B2, if c19=5, or the di erence B2-B1, if c19=6, is within the interval (c66,
c67), “reverse control is enabled on St1 and P1; outside of this temperature
range control is disabled.
St1
OUT2 OUT1
OUT
B1
P1
100%
0%
C19=5
c67-c65 c67
c66
c66+c65
ABILITAZIONE/
ENABLE
B2
ON
OFF
C19=6
c67-c65
c67
c66
c66+c65
ABILITAZIONE/
ENABLE
B2-B1
ON
OFF
Fig. 6.o
Direct” control with enable logic:
In this case too, a controller with two outputs, one of which a ON/OFF
and the other 0 to 10 Vdc. When the temperature read by probe B2, if
c19=5, or the di erence B2-B1, if c19=6, is within the interval (c66, c67),
direct control is enabled on St1 and P1; outside of this temperature
range control is disabled.
6.5.7 Independent operation (circuit 1+circuit 2)
(parameter c19=7)
Setting c19=7 control is “split” on two independent circuits, called circuit
1 and circuit 2, each with its own set point (St1, St2), di erential (P1, P2)
and PID parameters (ti_PID, td_PID).
This operation can only be set when c0=1 and 2 and is incompatible with
the activation of the operating cycle.
If c33=0, when setting c19=7 the control outputs are assigned to circuit 1
or circuit 2, depending on the model, as shown in the table below.
OUTPUT ASSIGNMENT
model circuit 1 (St1, P1) circuit 2 (St2, P2)
1 relay - -
2 relays OUT1 OUT2
4 relays OUT1, OUT2 OUT3, OUT4
4 SSRs OUT1, OUT2 OUT3, OUT4
1 relay +1 0 to 10 Vdc OUT1 OUT2
2 relays +2 0 to 10 V dc OUT1, OUT2 OUT3, OUT4
Tab. 6.h
Note that in general output 1 is always assigned to circuit 1, while output
2 can be assigned to circuit 1 or circuit 2. To assign any other output
to circuits 1 or 2, go to special operation (dependence=1 to assign the
outputs to circuit 1 and dependence= 2 to assign the outputs to circuit
2).
Example 1: con gure outputs 1, 2 to operate with direct logic using set
point and di erential 5, and outputs 3, 4 to operate with “reverse logic
with setpoint -5 and di erential 5.
Solution: set c0=1, c19=7, in this way St1 and P1 depend on probe B1 and
St2, P2 depend on probe B2. In addition St1=+5, P1=5 and St2=-5, P2=5.
Then activate special operation (c33=1) and set the activation and
di erential/logic for outputs 3 and 4 as follows:
OUT 3 OUT 4
Activation c44= -50 c48= -100
Di erential/logic c45= +50 c49= +50
Tab. 6.i
7,5 10St1=5
B1
ON
OUT1 OUT2
OFF
- 7,5-10 St2= - 5
B2
ON
OUT3OUT4
OFF
Fig. 6.p

Table of Contents

Other manuals for Carel ir33 Universale

Related product manuals