52
ENG
Control
WTS LARGE +0300131IT rel. 1.0 - 05.09.2022
11.6.14 Function test relay outputs
In this submenu you can check the relay outputs.
10 SOFTENER
11 CLEANING
11A WASHING
ENABLED
Display changes automatically
11D START PROD.
ENABLED
» Press the keys described below to switch the
relay.
UP é
Feed water valve
DN
ê
Permeate ush valve VPER
L
ç
Concentrate-ush valve VCONC
R
è
High pressure pump HP
E
Dosingpump Antiscalant PASC
» Press the key again to switch the relay back.
» Press ESC to return to the main menu
Notice:
To avoid damage to the unit: Always activate the feed
water valve é first before activating the pump è.
11.6.15 Function test alarm output
relay
In this submenu you can manually activate the alarm
output. The switched-on relay is then reset to its
switching status as programmed in submenu 12.
15 ALARM TEST
16 LANGUAGE
UP=ALARM
ESC=TEST EXIT
» Press “UP“ é, to switch the relay.
» Press the key again to switch the relay bac
» Press ESC to return to the main menu
11.6.16 Select language
In this submenu you can select the language shown on
the display.
16 LANGUAGE
17 SET PASSWORD
LANGUAGE
ENGLISH
» Press the arrow keys éê to select your
language
» Confirm the selection with
.
The program jumps back to the main menu