Devices that can be connected to the pCOXS 128KB (tLAN and Belimo versions)
Device
connector J6
connector J5
PCO1004850
PCOS004850
PCO100MDM0
PCO10000F0
PCO10000R0
PCO100CLP0
PCO1000WB0
PCO1000BA0
PCOS00HBB0
connector J7
connett. J8 (pCOXS tLAN)
connett. J8 (pCOXS Belimo)
Protocol active on the pCO Notes
PST terminal X PST terminal Incompatible with tLAN Master 5 expansions
PLD terminal X
pCOT - pCOI terminal X Local terminal or pLAN
pGD0 - pGD1 terminal X Local terminal or pLAN With Local terminal the pGD* works in pCOT emulation mode
pGD2 - pGD3 terminal X Local terminal or pLAN
Aria terminal X
pCO in pLAN X pLAN
FCM series controllers X
EVD200 X
EVD400 X X
pLAN or CAREL Master or
CAREL Master 5 exp.
Can only be activated on one serial port. CAREL Master 5 exp.: incompatible
with PST terminal
CAREL Slave devices (tLAN) X
CAREL Master or CAREL
Master 5 exp.
Can only be activated on one serial port. CAREL Master 5 exp.: incompatible
with PST terminal
CAREL Slave devices (RS485) X X X
CAREL Master or
CAREL Master: can only be activated on one port, BMS serial or FieldBus
serial.
pCOexp 485 X X X
CAREL Master 5 exp.
CAREL Master 5 exp.: can only be activated on one port, pLAN serial or
FieldBus serial
pCOexp tLAN X CAREL Master 5 exp.
Can only be activated on one port, pLAN serial or FieldBus serial
μChiller2 expansion
X
Hydronic fan coil and CANbus X CAREL Master
Can only be activated on one port, BMS serial or FieldBus serial
PlantVisor local X X X
PlantWatch X X X
PCGate X X X
WebGate X X X Can only be activated on one serial port
GATEWAY**0 X X X
LON - Echelon RS485 X Incompatible with protocols
LON - Echelon FTT10 X CAREL Slave PSTN
TREND X GSM
HTTP client X Modbus Slave
BACnet/Ethernet X
BACnet/IP X
BACnet/MSTP (RS485) X
SNMP v1, SNMP v2C X
SNMP v3 X For SNMP v3 special pCOWEB software is used
Modbus supervisor (RTU) X X X Modbus Slave
Incompatible with CAREL Slave, PSTN, GSM
Modbus Slave devices X X X Modbus Master Can only be activated on one serial port
pCOexp Modbus X X X
BenShaw devices X X Modbus Master - Benshaw Maximum of two Benshaw devices
WinLoad local XXXX WinLoad Can only be activated on 1 serial. Incompatible with PSTN & GSM
WinLoad remote, analogue modem X PSTN Incompatible with CAREL Slave and Modbus Slave
PlantVisor remote, analogue modem X
WinLoad remote, GSM modem X
PlantVisor remote, GSM modem X GSM Incompatible with CAREL Slave and Modbus Slave
Send and receive SMS X
Belimo devices (max 8) X MP-Bus
Maximum of 8 devices
Serial printer X Serial printer
73
serial 0 -
pLAN serial 1 - BMS
serial 2 -
FieldBus